10 ecm alarm interface & communications, 9 ecm apu control interface, Top view plug-side view wire-insertion-side view – Alpha Technologies AlphaGen PN-6x-T 7.5kW 48VDC - Installation and Operation Manual User Manual

Page 78

Advertising
background image

78

745-020-B0-003, Rev. C

Fig. 8-9, APU Control Interface

8.10 ECM Alarm Interface & Communications

Terminal 1

Top View

Plug-side View

Wire-insertion-side View

Terminal 1

Terminal 1

Fig. 8-10, ECM, SCM Connector Arrangement

Pin

Description

Function

1

+12V Ignition Battery

Ignition Battery Fused 12V from APU

2

Neg. Ignition Battery

Ignition Battery Negative from APU

3

Low Oil Pressure

Active LOW signal denotes low oil pressure.

4

Over-temp

Active LOW signal indicates Over-temp.

5

Start Command

Active LOW from ECM activates APU Start relay.

6

Common (Start – Stop)

Common return between START and STOP relays.

7

Stop Command

Active LOW from ECM activates APU Stop relay.

8

Over-speed

Active LOW signal denotes engine RPM was exceeded.

9

Over-crank

Active LOW signal denotes Over-crank Limit is reached.

10

Engine Run

Active LOW signal denotes the engine is running.

11

Not Used

12

Not Used

8.0 Interconnection,

continued

8.9 ECM APU Control Interface

The interface control is a 12-pin (2x6 row) Mini Mate-’N’-Lok style connector.

J4

RE A R

V I E W

WI RE

SI DE

RE A R
V I E W