0 interconnection, 1 gas hazard alarm interface connector, 2 low fuel pressure interface connector – Alpha Technologies AlphaGen PN-6x-T 7.5kW 48VDC - Installation and Operation Manual User Manual

Page 74

Advertising
background image

74

745-020-B0-003, Rev. C

Fig. 8-1, Gas Hazard Detector Interface Connector

Fig. 8-2, Low Fuel Pressure Interface Connector

Pin Description

Function

1

Gas Hazard Sensor Switch

Active OPEN signal denotes gas hazard (Logic HIGH)

2

Gas Hazard Power/Alarm Common

Return signal path for sensor

3

Gas Hazard Logic Power +12VDC Fused

Logic Power for Logic PCB & sensor

8.0 Interconnection

8.1 Gas Hazard Alarm Interface Connector

The Gas Hazard Detector Interface Connector is connected between the wire harness and
detector unit as shown. The interface control is a 3-pin (1x3 row) Universal Mini Mate-’N’-Lok
style male connector.

REAR
VIEW

REAR
VIEW

TO

ECM

FROM

SENSOR

Rear view, wire side

TO

ECM

FROM

LOW

FUEL

SENSOR

Rear view, wire side

8.2 Low Fuel Pressure Interface Connector

The interface control is a 2 pin Mini Mate-'N’-Lok connector (near gas solenoid):

Pin 1 = +12VDC activates (opens) solenoid ONLY when APU is running. Controlled by
APU engine ON command

Pin 2 = Low fuel pressure switch (negative)

Pin

Description

Function

1

Low Fuel Pressure Sensor Contact

Closed (LOW signal) denotes Low
Fuel Pressure (LP Versions only)

2

Low Fuel Pressure Common

Return signal path for sensor