10 final inspection checklist – Alpha Technologies AlphaGen PN-6x-T 7.5kW 48VDC - Installation and Operation Manual User Manual

Page 36

Advertising
background image

36

745-020-B0-003, Rev. C

3.0 Installation,

continued

3.10 Final Inspection Checklist

Alpha recommends setting the ECM Run/Auto/Stop (RAS) switch to the STOP position before
initially powering up the ECM. This allows the operator to control the START and STOP functions of
the APU until the system is set up. This also prevents the APU from starting unexpectedly.

CAUTION!

Once the installation has been completed verify the following:

1. Engine oil at proper level.

2. All electrical connections securely made.

3. Engine Control Module (ECM) set to STOP.

4. Battery connections made.

5. Battery voltage normal.

6. Gas connections checked for leak integrity.

7. Gas pressure normal.

When the above test/checks have been made, the unit is ready for initial turn-up.

Advertising