65
Remove Screw
7.0 Maintenance,
continued
7.5 Replacing Ignition Battery Charger Module Assembly
Required Tools:
#2 Phillips screwdriver
The 48VDC charger module is located above the ECM housing.
1. Disconnect the connectors from the front of the module.
2. Remove the Phillips screw holding the front of the charger to the ECM housing.
3. The back of the charger is held in place by a tab that fi ts into a slot on to the ECM
housing. Slide the charger free and lift it out of the enclosure.
Fig. 7-4, Ignition Battery Charger