6 inverter battery dc sense interface connector, 5 ecm enclosure alarm interface connector – Alpha Technologies AlphaGen PN-6x-T 7.5kW 48VDC - Installation and Operation Manual User Manual

Page 76

Advertising
background image

76

745-020-B0-003, Rev. C

Fig. 8-5, ECM Enclosure Alarm Interface Connector

8.6 Inverter Battery DC Sense Interface Connector

ECM - Inverter Battery DC Sense Interface Connector J8. The interface control is a 3-pin (1x3
row) Mini Mate-’N’-Lok style connector.

Fig. 8-6, Inverter Battery DC Sense Interface Connector

Pin

Description

Function

1

Water Intrusion Sensor

Contact OPEN (HIGH signal) denotes water

2

Water Intrusion common

Return signal path for sensor

3

Pad Shear Sensor

Contact CLOSED (LOW signal) denotes pad shear

4

Pad Shear Common

Return signal path for sensor

5

Low Fuel Pressure Sensor

Contact CLOSED (LOW signal) denotes low fuel
pressure (LP versions only)

6

Low Fuel Pressure Common

Return signal path for sensor

7

Gas Hazard Sensor Switch

Active OPEN signal denotes gas hazard (Logic HIGH)

8

Gas Hazard Power/Alarm

Return signal path for sensor (Common)

9

Gas Hazard Logic Power

Logic power for Logic PCB & sensor (+12VDC Fused)

10

Door Open Sensor

Contact CLOSED (LOW signal) denotes door is open

11

Door Open Common

Return signal path for sensor

12

No Connection

13

+12V Fused

LPG fuel monitor

14

Common

Return path for LPG fuel monitor

8.0 Interconnection,

continued

8.5 ECM Enclosure Alarm Interface Connector

The Alarm Interface Connector (J10) is connected to the Power PCBA. The interface control
is a 14-pin (2x7 row) Universal Mini Mate-’N’-Lok style male connector.

REAR

VIEW

WIRE

SIDE

J10

REAR
VIEW

Pin

Description

Function

1

DC Bus Sense (POS.)

Output inverter battery bus – positive connection, 48 and 98VDC buses

2

No Connection

3

DC Bus Sense ( NEG.)

Output inverter battery bus – positive connection, 48 and 96VDC buses

REAR
VIEW

REAR

VIEW

WIRE

SIDE

J8

Advertising