3.0 Installation,

continued

3.9 Terminal Block 2 (AC Line) Connections

Terminal Block 2 is located in the rear of the enclosure, next to the convenience outlet.
Connect the user-supplied wiring using a #1 fl at-head screwdriver. Strip wires 3/8" (9.5mm)
and torque to 7 in-lbs (0.8 Nm). Refer to the table and photo below for alarm defi nitions.

Terminal Block 2

Pos #

Function

23

Major Alarm NO

22

Major Alarm NC

21

Major Alarm Com

20

*Special Use

19

Alarm Bypass Com

18

Alarm Bypass NO

17

Alarm Bypass NC

16

Eng Run Com

15

Eng Run Com NO

14

Eng Run Com NC

13

Minor Alarm NO

12

*Special Use

11

Minor Alarm COM NO

10

Door NO

9

Door COM

8

LPG Monitor PWR (-12V)

7

LPG Monitor PWR (+12V)

6

AC Line Fail NC

5

AC Line Fail NO

4

AC Line Fail COM

3

AC Input Ground

2

AC Input Neutral

1

AC Input Line

Fig. 3-11, Terminal Block 2 (TB2)

Table 3-1, Terminal Block 2 (TB2) Connections

Terminal Block 2

Position 1

*For customers requiring Normally Closed (NC) logic minor alarm, make connections to TB2 positions 12 and
20.