7.0 Maintenance,

continued

7.8 Gas Solenoid Replacement Procedure

Required Tools and Materials:

• Crescent

wrench

Pipe thread compound

Leak detector compound (soapy water)

Two people are required to perform this procedure. To replace the fuel solenoid, the entire
regulator package must be replaced.

1. Ensure the fuel supply is disconnected from the input regulator.

2. Remove the pre-regulator at the connection to the right of the solenoid.

3. Remove

the

fl exible hose from the load block.

4. Remove the two mounting screws from the demand regulator.

5. Remove the demand regulator and solenoid assembly from the enclosure.

6. Reinstall new equipment in reverse order.

7. Check all new connections for leaks.

Fig. 7-10, Fuel Solenoid Valve

Regulator

Mounting Screw

Regulator

Mounting Screw

Input Regulator

Connection