8 gas solenoid replacement procedure – Alpha Technologies AlphaGen PN-6x-T 7.5kW 48VDC - Installation and Operation Manual User Manual
Page 69

745-020-B0-003, Rev. C
69
7.0 Maintenance,
continued
7.8 Gas Solenoid Replacement Procedure
Required Tools and Materials:
• Crescent
wrench
•
Pipe thread compound
•
Leak detector compound (soapy water)
Two people are required to perform this procedure. To replace the fuel solenoid, the entire
regulator package must be replaced.
1. Ensure the fuel supply is disconnected from the input regulator.
2. Remove the pre-regulator at the connection to the right of the solenoid.
3. Remove
the
fl exible hose from the load block.
4. Remove the two mounting screws from the demand regulator.
5. Remove the demand regulator and solenoid assembly from the enclosure.
6. Reinstall new equipment in reverse order.
7. Check all new connections for leaks.
Fig. 7-10, Fuel Solenoid Valve
Regulator
Mounting Screw
Regulator
Mounting Screw
Input Regulator
Connection