75

Fig. 8-3, Gas Solenoid Interface Connector

Fig. 8-4, Charger Control Interface Connector

8.4 48V Charger Module Control Interface Connector

The Charger Module – Control Interface Connector is connected between the
charger module and ECM with Sense/Power leads connected to the APU output DC bus. The
interface control is a 4-pin (2x2 row) Universal Mini Mate-’N’-Lok style male connector.

8.0 Interconnection,

continued

8.3 Gas Solenoid Interface Connector

Vapor

Fuel

Solenoid

FROM APU

Connection

is not

polarized

Pin

Description

Function

1

ECM Charger Control
(+) Yellow Wire

Connects pins 1 and 2 together, turning the charger
ON, i.e. Closed (LOW signal).

2

Inverter Battery
(+) Red Wire

Input power to charger module, operates on 48VDC
battery pack to charge ignition battery.

3

ECM Charger Control
Orange Wire

ECM Turns charger ON by applying a LOW signal to
this pin (referenced to ignition battery negative).

4

Inverter Battery (-)
Black Wire

NEGATIVE Input power to charger module, operates
on 48VDC battery pack to charge ignition battery.

REAR
VIEW

Pin

Description

Function

1

Gas Solenoid +12V

+12VDC supplied to Gas Solenoid only when APU is ON
(Running). APU Shuts OFF gas supply to cabinet during
any fail safe or fault condition.

2

Gas Solenoid Common

Return path for Gas Solenoid.