Alpha Technologies AlphaGen PN-6x-T 7.5kW 48VDC - Installation and Operation Manual User Manual

Page 48

Advertising
background image

48

745-020-B0-003, Rev. C

4.0

The Engine Control Module, continued

4.8

ECM DIP Switch and Fuse Confi guration, continued

Table 4-4, DIP Switch Settings

Programming parameters that affect the Autotest feature via status monitoring will override this switch setting.
To reset factory defaults, turn all DIP switches off, power up the ECM (plug in AC line sense) for 10 seconds,
remove power, then reset DIP switches.

ON

1 2 3 4 5

6 7

8

Interface

Output Voltage Confi guration

Input Voltage Confi guration

Engine Start/Run Signal

Enable Autotest

Fig. 4-7, SW5 Settings

NOTE:

ECM SW5 Settings

Meaning

1

2

3

4

5

6

7

8

1 = ON, 0 = OFF

0

Non standard GRI interface
(7.5kW Series)

1

Standard GRI interface

0

0

0

Invalid output voltage configuration

0

0

1

24VDC Output

0

1

0

36VDC Output

0

1

1

48VDC Output

1

0

0

96VDC Output

1

0

1

120VDC Output

1

1

0

208VDC Output

1

1

1

240VDC Output

0

0

Invalid input voltage configuration

1

0

120AC input

0

1

208 3-phase input

1

1

240VAC input

0

0

No effect

1

0

No effect

1

0

ECM Drives starter with the "Engine Start"
Signal.

1

1

"Engine Start" Signal becomes
"Engine Run" and is held low by ECM

0

Autotest turned OFF.*

1

Autotest sequence enabled with 14-day test
interval