7 connecting the alarm and control connections – Alpha Technologies AlphaGen PN-6x-T 7.5kW 48VDC - Installation and Operation Manual User Manual

Page 46

Advertising
background image

46

745-020-B0-003, Rev. C

4.0

The Engine Control Module, continued

4.7 Connecting the Alarm and Control Connections

The Alarm output interface and communications connectors are shown below.

Fig. 4-4, RS-488 (AlphaBus) Communications Input Connector

Pin 1

Fig. 4-5, Terminal Block 1

Terminal Block 1

Pin

Alarm Signal Description

Alarm Active State

1

Engine Run Common

N/A

2

Engine Run

Closed with respect to Pin 1

3

Engine Run

Open with respect to Pin 1

4

Major Alarm Common

N/A

5

Major Alarm

Closed with respect to Pin 4

6

Major Alarm

Open with respect to Pin 4

7

Minor Alarm Common

N/A

8

Minor Alarm

Closed with respect to Pin 7

9

Minor Alarm

Open with respect to Pin 7

10

Not used

Not used

11

Not used

Not used

12

Not used

Not used

Pin 1

TB 1