4.0
The Engine Control Module, continued
4.7 Connecting the Alarm and Control Connections
The Alarm output interface and communications connectors are shown below.
Fig. 4-4, RS-488 (AlphaBus) Communications Input Connector
Pin 1
Fig. 4-5, Terminal Block 1
Terminal Block 1
Pin
Alarm Signal Description
Alarm Active State
1
Engine Run Common
N/A
2
Engine Run
Closed with respect to Pin 1
3
Engine Run
Open with respect to Pin 1
4
Major Alarm Common
N/A
5
Major Alarm
Closed with respect to Pin 4
6
Major Alarm
Open with respect to Pin 4
7
Minor Alarm Common
N/A
8
Minor Alarm
Closed with respect to Pin 7
9
Minor Alarm
Open with respect to Pin 7
10
Not used
Not used
11
Not used
Not used
12
Not used
Not used