WARNING! The Model 7xD, 7xR or 7xT overfill probes should be

used for Safety Shutdown/Overfill applications. All other
Guided Wave Radar probes should be installed so the
maximum overfill level is a minimum of 6" (150 mm)
below the process connection. This may include utilizing
a nozzle or spool piece to raise the probe. Consult
factory to ensure proper installation.

WARNING! Do not disassemble probe when in service and under

pressure.

2.4.1 Installing a Coaxial Probe

(Models 7xA, 7xD, 7xG, 7xP, 7xR, 7xS, and 7xT)

Before installing, make sure the:

• Model and serial numbers on the nameplates of the

ECLIPSE probe and transmitter are identical.

• Probe has adequate room for installation and has unob-

structed entry to the bottom of the vessel. The Model 7xD
(High Temp./High Pressure) probe, Model 7xP (High
Pressure) probe, Model 7xR (Overfill) probe, Model 7xS
(Steam) probe and Model 7xT (Interface) probe require
added clearance. See Physical Specifications, Section 3.6.6.

• Process temperature, pressure, dielectric, and viscosity are

within the probe specifications for the installation.
See Specifications, Section 3.6.

• Model 7xD (High Temp./High Pressure) probes should be

handled with extra care due to the ceramic spacers used
throughout their length.

• Model 7xG (caged GWR) probes should be handled

with extra care. Only handle these probes by the flanges.

2.4.1.1 To install a coaxial probe:

x Make sure the process connection is at least

3

⁄

4

" NPT or a

flanged mounting.

y Carefully place the probe into the vessel. Align the gasket

on flanged installations.

z Align the probe process connection with the threaded or

flanged mounting on the vessel.

{ For threaded connections, tighten the hex nut of the probe

process connection. For flanged connections, tighten flange
bolts.

NOTE: If the transmitter is to be installed at a later time, do not remove

the protective cap from the probe. Do not use sealing com-
pound or TFE tape on probe connection to transmitter as this
connection is sealed by a Viton

®

O-ring.

NOTE: For applications using the Model 7xS steam probe, it is manda-

tory to keep the transmitter and probe matched as a set.

y

x

{

z

57-600 Eclipse

®