10

WARNING! The Model 7xD, 7xR or 7xT overfill probes should be

used for Safety Shutdown/Overfill applications. All other
Guided Wave Radar probes should be installed so the
maximum overfill level is a minimum of 6" (150 mm)
below the process connection. This may include utilizing
a nozzle or spool piece to raise the probe. Consult
factory to ensure proper installation.

WARNING! Do not disassemble probe when in service and under

pressure.

2.4.1 Installing a Coaxial Probe

(Models 7xA, 7xD, 7xG, 7xP, 7xR, 7xS, and 7xT)

Before installing, make sure the:

• Model and serial numbers on the nameplates of the

ECLIPSE probe and transmitter are identical.

• Probe has adequate room for installation and has unob-

structed entry to the bottom of the vessel. The Model 7xD
(High Temp./High Pressure) probe, Model 7xP (High
Pressure) probe, Model 7xR (Overfill) probe, Model 7xS
(Steam) probe and Model 7xT (Interface) probe require
added clearance. See Physical Specifications, Section 3.6.6.

• Process temperature, pressure, dielectric, and viscosity are

within the probe specifications for the installation.
See Specifications, Section 3.6.

• Model 7xD (High Temp./High Pressure) probes should be

handled with extra care due to the ceramic spacers used
throughout their length.

Model 7xG (caged GWR) probes should be handled

with extra care. Only handle these probes by the flanges.

2.4.1.1 To install a coaxial probe:

x Make sure the process connection is at least

3

4

" NPT or a

flanged mounting.

y Carefully place the probe into the vessel. Align the gasket

on flanged installations.

z Align the probe process connection with the threaded or

flanged mounting on the vessel.

{ For threaded connections, tighten the hex nut of the probe

process connection. For flanged connections, tighten flange
bolts.

NOTE: If the transmitter is to be installed at a later time, do not remove

the protective cap from the probe. Do not use sealing com-
pound or TFE tape on probe connection to transmitter as this
connection is sealed by a Viton

®

O-ring.

NOTE: For applications using the Model 7xS steam probe, it is manda-

tory to keep the transmitter and probe matched as a set.

y

x

{

z

57-600 Eclipse

®

Guided Wave Radar Transmitter