1.1.2 Configuration Information

Some key information is needed to configure the
ECLIPSE transmitter. Complete the following operating
parameters table before beginning configuration.

Display

Question

Answer

Probe Model

What probe model is listed on the
model information?
(first four digits of probe model number)

_____________

Probe Mount

Is the probe mounted NPT, BSP,
or flange?

_____________

Measurement

What is the desired measurement? Choices

Type

are: Level only, volume, interface level
or interface level and volume.

_____________

Level Units

What units of measurement will be
used? (inches, centimeters, feet or meters)

(AI block parameter. Not selectable at
transmitter on Model 705 Fieldbus)

_____________

Probe Length

What probe length is listed on the
model information?

_____________

Level Offset

The desired level reading when the
liquid is at the end of the probe.

_____________

Dielectric

What is the dielectric constant range
of the process medium? (Upper layer
dielectric for interface applications
)

_____________

Loop Control

Is the output current to be controlled
by level or volume?

_____________

Set 4.0 mA

What is the 0% reference point for the
4.0 mA value? (EU_0 value for
F

OUNDATION

fieldbus)

_____________

Set 20.0 mA

What is the 100% reference point for
the 20.0 mA value? (EU_100 value for
F

OUNDATION

fieldbus)

_____________

(Top 6" (152 mm) of Single Rod probes is within

Blocking Distance)

1.2

QuickStart Mounting

NOTE: Confirm the configuration style and process connection

size/type of the ECLIPSE transmitter. Ensure it matches the
requirements of the installation before continuing with the
QuickStart installation.

x Confirm the model and serial numbers on the nameplates

of the ECLIPSE probe and transmitter are identical.

NOTE: For applications using the Model 7xS steam probe, it is manda-

tory to keep the transmitter and probe matched as a set.

1.2.1 Probe

y Carefully place the probe into the vessel. Align the probe

process connection with the threaded or flanged mounting
on the vessel.

x

{

}

|

~

y

z

x

5

57-600 Eclipse

®

Guided Wave Radar Transmitter