25

57-600 Eclipse

®

Guided Wave Radar Transmitter

2.6.5.2 Measurement Type: Level and Volume (Loop Control = Volume)

Display

Action

Comment

22

SZ Fault
(select)

Select loop current behavior
when level is sensed in safety
zone

Safety Zone is a user-defined area just below the Blocking
Distance
. Enable Fault if necessary to ensure safe, reliable high-
level readings in critical applications. Choices are None, 3.6 mA,
22 mA, Latch 3.6 or Latch 22. If Latch 3.6 or Latch 22 is
selected, the loop current will remain in alarm until it is manually
cleared with the SZ Alarm Reset below (#23)

23

SZHeight

xx.x lu

Enter distance below
BlockDis where SZ Fault will
be asserted

Enter a distance value that develops a safety zone just below the
Blocking Distance. Here the unit will report a Safety Zone Fault
(#21) if the level rises into this area.

24

SZ Alarm Reset

Press Enter to clear a
latched Safety Zone alarm

Clear a latched Safety Zone alarm

25

Threshld
(select)

Select the type of threshold

Unit default CFD. Only select Fixed in application with low
dielectric material over higher dielectric material and unit is read-
ing incorrect level. Example: Oil over water. (Adjustment of Trim
Level
may be necessary when threshold is changed)

26

Poll Adr

xx

Enter HART polling address
number (0-63)

Select a HART poll address (0–63). Enter 0 for a single
transmitter installation. Poll address does not affect loop current.

27

Loop Mode

Enable/Disable

Determines whether the loop is fixed at 4.0 mA or controlled by
the PV.

28

Trim Lvl

xx.x lu

Enter value to adjust Level
reading

-10.0 inches <= Lvl Trim <= +10.0 inches
(Requires superuser password)

29

Trim 4

xxxx

Fine tune the 4 mA point

Adjust setting to output exactly 4.0 mA on current meter

30

Trim 20

xxxx

Fine tune the 20 mA point

Adjust setting to output exactly 20.0 mA on current meter

31

Loop Tst

xx.x mA

Enter a mA Output value

Set mA output to any given value to perform loop test

32

LvlTicks

xxxx

Diagnostic Display

Time of flight from fiducial to level signal

33

New Pass

xxx

Enter new password (0-255)

Displays encrypted value of present password

34

Language
(select)

Select from English, Spanish,
French, German

Language choice for LCD display

35

Mdl705HT
Ver3.0a0

Transmitter display

Product identification Firmware version

36

DispFact
(select)

Select Yes to display factory
parameter menus

Allows for viewing the factory parameters

37

History

(current status)

Press Enter to view history
of recent exceptions

Diagnostic Display

38

HF cable
(select)

Superuser Parameter

Select from 3-foot or 12-foot remote

39

Run Time

40

History Reset

Press Enter and select yes
to clear history

Similar to SZ Alarm Reset

41

FidTicks

xxxx

Diagnostic Display

Time of flight from start of ramp to fiducial

42

Fid Type
(select)

Superuser Password

Select from positive or negative
(Selection only allowed for some probes)

43

Fid Spread