2 performance - model 705 – Orion Instruments Eclipse 705 User Manual

Page 53

Advertising
background image

53

Reference Conditions



Reflection from water at +70° F (+20° C) with 72" coaxial probe

(CFD threshold)

Linearity

Ž

Coaxial/Twin Rod Probes:

<0.1% of probe length or 0.1 inch (whichever is greater)

Single Rod Probes:

<0.3% of probe length or 0.3 inch (whichever is greater)

Measured Error

Coaxial/Twin Rod Probes:

±0.1% probe length or ±0.1 inch (whichever is greater)

Single Rod Probes

±0.5% probe length or ±0.5 inch (whichever is greater)

Resolution

±0.1 inch

Repeatability

<0.1 inch

Hysteresis

<0.1 inch

Response Time

<1 second

Warm-up Time

<5 seconds

Operating Temp. Range

-40° to +175° F (-40° to +80° C)

LCD Temp. Range

-5° to +160° F (-20° to +70° C)

Ambient Temp. Effect

Approximately +0.02% of probe length/ ° C

Process Dielectric Effect

<0.3 inch within selected range

Humidity

0-99%, non-condensing

Electromagnetic Compatibility

Meets CE requirements: EN 61326

(Twin and Single Rod probes must be used in metallic vessel or

stillwell to maintain CE requirement)

3.6.2 Performance - Model 705

 Specifications will degrade with Model 7xB, 7xD, and 7xP probes and/or Fixed threshold configuration.
Ž Top 24 inches of Model 7xB probe: 1.2 inches (30 mm). Specification for top 48 inches of single rod will

be application dependent.

57-600 Eclipse

®

Guided Wave Radar Transmitter

Environment

Operating Temperature

-40 to +175° F

(-40 to +80° C)

Display Function Operating Temperature

-5 to +160° F

(-20 to +70° C)

Storage Temperature

-50 to +175° F

(-46 to +80° C)

Humidity

0-99%, non-condensing

Electromagnetic Compatibility

Meets CE Requirements: EN 61326

Note: Twin Rod and Single Rod probes must be used in metallic vessel

or stillwell to maintain CE requirement.

Mounting Affects: Twin Rod

Active rod must be mounted at least 1" (25 mm) from any surface or

obstruction. Minimum stillwell diameter for Twin Rod probe is 3".

Single Rod

Nozzles do not restrict performance by ensuring the following:

No nozzle is <2" (50 mm) diameter

Ratio of Diameter: Length is 1:1 or greater;

any ratio <1:1 (e.g., a 2"

× 6" nozzle = 1:3) may require a Blocking

Distance and/or DIELECTRIC adjustment (see Section 2.6.5)

No pipe reducers are used

Obstructions (See Probe Clearance Table, page 47)

Keep conductive objects away from probe to ensure proper performance

Shock Class

ANSI/ISA-S71.03 Class SA1

Vibration Class

ANSI/ISA-S71.03 Class VC2

SIL 3 Capable

Safe Failure Fraction (SFF) 91%