3 performance - model 705 interface, 4 process conditions – Orion Instruments Eclipse 705 User Manual

Page 54

Advertising
background image

54

57-600 Eclipse

®

Guided Wave Radar Transmitter

Reference Conditions

Reflection from liquid of selected dielectric at +70° F (+20° C) with 72" probe

Linearity

<0.5 inch

Measured Error

Upper layer ±1 inch

Interface layer ±1 inch (clean distinct interface required)

Upper Layer Dielectric

1.4–5.0

Interface Layer Dielectric

>15

Resolution

±0.1 inch

Repeatability

<0.5 inch

Hysteresis

<0.5 inch

Response Time

<1 second

Warm-up Time

<5 seconds

Operating Temp. Range

-40° to +175° F (-40° to +80° C)

LCD Temp. Range

-5° to +160° F (-20° to +70° C)

Ambient Temp. Effect

Approximately ±0.02% of probe length/ ° C

Humidity

0-99%, non-condensing

Electromagnetic Compatibility

Meets CE requirements: EN 61326

3.6.3 Performance - Model 705 Interface

Model

Coaxial

(7xA, 7xG, 7xT, 7xR)

Twin Rod

(7xB)

HTHP Coaxial

(7xD)

HP Coaxial

(7xP)

Steam

Œ

(7xS)

Maximum

Process Temperature

7xA:

+300° F @ 400 psig

(+150° C @ 27 bar)

7xG, 7xT & 7xR:

+400° F @ 270 psig

(+200° C @ 18 bar)

+400° F @ 275 psig

(+200° C @ 19 bar)

+800° F @ 1500 psig

(+427° C @ 103 bar)

+400° F @ 5500 psig

(+200° C @ 380 bar)

+650° F @ 2400 psig

(+340° C @ 165 bar)

Maximum

Process Pressure

1000 psig @ +70° F

(70 bar @ +20° C)

1000 psig @ +70° F

(70 bar @ +20° C)

6250 psig @ +70° F

(430 bar @ +20° C)

6250 psig @ +70° F

(430 bar @ +20° C)

3000 psig @ +100° F

(207 bar @ +38° C)

Maximum Viscosity

500 cp (Standard)

1500 cp (Enlarged)

10,000 Caged Coaxial

1500 cp

500 cp (Standard)

1500 cp (Enlarged)

500 cp (Standard)

1500 cp (Enlarged)

500 cp

Dielectric Range

≥1.4

≥1.9

≥1.4

≥1.4

>10

Hermeticity

N/A

N/A

Helium leak rate <10

-8

cc/sec

@ 1 atmosphere vacuum

N/A

Model

Rigid

(7xF)

Rigid

(7xJ)

Flexible

(7x1)

Flexible

(7x2, 7x5)

Hygienic

(7xF-E)

Paint

(7xF-P)

Maximum

Process Temperature

+300° F @ 400 psig

(+150° C @ 27 bar)

+605° F @ 1600 psig

(+320° C @ 110 bar)

+300° F @ 400 psig

(+150° C @ 27 bar)

+150° F @ 50 psig
(+66° C @ 3.4 bar)

+300° F @ 75 psig

(+150° C @ 27 bar)

160° F

(71° C)

Maximum

Process Pressure

1000 psig @ +70° F

(70 bar @ +20° C)

3550 psig @ +70° F

(245 bar @ +20° C)

N/A

75 psig @ +300° F

Atmospheric

Maximum Viscosity

10,000

(consult factory if severe agitation/turbulence)

2000

Dielectric Range

≥1.9

Hermeticity

N/A

3.6.4 Process Conditions

ΠNot for direct insertion into boilers.

Advertising