3.3.2 Status Messages

Display Message

Action

Comment

OK

None

Normal operating mode

Initial

None

Program is Initializing, level reading held at 4 mA set point. This is a
transient condition.

DryProbe

None

Normal message for a dry probe. End of probe signal is being detected.

EOP < Probe

Length

End of Probe signal from a dry
probe is out of range

1) Ensure probe length is entered correctly

2) Set transmitter to a lower dielectric range

3) Consult factory

4) Ensure proper blocking distance

EOP High

End of Probe signal is out of
range

1) Ensure probe length is entered correctly

2) Consult factory (old twin rod probe being used with enhanced 705)

WeakSgnl

None. Signal amplitude is lower
than desired.

1) Set transmitter to lower dielectric range

2) Increase sensitivity

Flooded?

Loss of level signal possibly
due to flooding, twin rod
probes only

1) Decrease level in vessel

2) Set transmitter to lower dielectric range

3) Replace with Model 7xR Overfill probe

NoSignal

No level signal being detected

1) Ensure dielectric setting is correct for measured medium

2) Increase sensitivity

3) Confirm that the probe type is proper for the dielectric of the medium

4) Consult factory

No Fid

Fiducial signal is not being
detected

1) Check connection between probe and transmitter

2) Check for moisture on top of probe

3) Check for damaged gold pin on the high frequency connector

4) Consult factory

FidShift

FidTicks shifted from expected
value

1) Check connection between probe and transmitter

2) Check for moisture on top of probe

3) Check for damaged gold pin on the high frequency connector

4) Consult factory

Fid Sprd*

Fiducial Ticks variation is
excessive

1) Check connection between probe and transmitter

2) Check for moisture on top of probe

3) Consult factory

SZ Alarm

Safety Zone alarm has been
tripped, loop current fixed at
SZ Fault

Decrease level in vessel

Hi Temp

Present temperature in
electronics compartment is
above +80° C

1) Transmitter may need to be moved to ensure ambient temperature

is within specification

2) Change to remote mount transmitter