Orion Instruments Eclipse 705 User Manual

Page 27

Advertising
background image

27

57-600 Eclipse

®

Guided Wave Radar Transmitter

2.6.5.3 Measurement Type: Interface Level (Loop Control = Interface Level)

Display

Action

Comment

1

*Status*
*IfcLvl*

*% Out *
* Loop *

Transmitter Display

LoopCtrl = IfcLevel
Transmitter default display showing Status, IfcLevel, % Output,
and Loop values cycles every 5 seconds

2

IfcLvl

xxxx vu

Transmitter Display

Transmitter displays interface level in selected units

3

% Output

xx.x%

Transmitter Display

Transmitter displays % Output measurement derived from
20 mA span

4

Loop

xx.xx mA

Transmitter Display

Transmitter displays Loop value (mA)

5

Level

6

PrbModel
(select)

Select the type of probe
used

(Example: 7xT-x)

Select from 7xB-x, 7xD-x, 7xF-x, 7xG, 7xL, 7xM, 7xN, 7xT-x,
7x7-x
as shown on the probe nameplate

7

PrbMount
(select)

Select the type of probe
mounting

Select from NPT, BSP, or Flange

8

MeasType
(select)

Select type of measurement

Select from Intrface

9

LvlUnits
(select)

Select level units

Select from cm, inches, feet or meters

10

Probe Ln

xxx.x

Enter the exact length of
probe

Probe length is printed on the nameplate and order information
and is the last three digits of the probe model number

11

Lvl Ofst

x.xx

Enter the desired reading
when probe is dry

Level Offset is the distance from the probe tip to the desired 0%
level point (-90 to 300"). Refer to Section 2.6.6

12

Upr Diel
(select)

Enter the dielectric constant
of the upper liquid

Interface mode or Manual compensation mode

13

Dielctrc
(select)

Select range bounding the
dielectric constant of the
lower liquid

Select 10–100

14

Senstvty

xxx

Enter value upward or
downward to sense liquid
surface

Allows fine gain adjustment for single rod probes (this parameter
is password protected for coaxial and twin rod probes)

15

LoopCtrl
(select)

Select variable to control
loop current

Select from Level or IfcLvl

16

Set 4mA

xxx.x 1u

Enter the PV value for the
4 mA point

A small transition zone (0–6") may exist at the top/bottom of
the probe. See Functional Specifications Probe, Section 3.6.1

17

Set 20mA
xxx.x lu

Enter the PV value for the
20 mA point

A small transition zone (0–6") may exist at the top/bottom of
the probe

18

Damping

xx s

Enter time constant of
desired damping

A Damping factor (0–10 seconds) may be added to smooth the
output due to turbulence

19

Fault

(select)

Select the loop current value
in presence of a fault

Select from 3.6 mA, 22 mA or HOLD

20

BlockDis

xx.x lu

Enter distance below
reference point where
level is not sensed

Allows user to ignore level measurements near the top of probe