6 offset description, Example 1, Example 2 – Orion Instruments Eclipse 705 User Manual

Page 33: Example 3

Advertising
background image

33

57-600 Eclipse

®

Guided Wave Radar Transmitter

2.6.6 Offset Description

The parameter referred to as Lvl Ofst in the ECLIPSE menu
is the desired level reading when liquid surface is at the end
of the probe. The ECLIPSE transmitter is shipped from the
factory with Lvl Ofst set to 0. With this configuration, all
measurements are referenced from the bottom of the probe.
See Example 1.

Example 1 (Lvl Ofst = 0 as shipped from factory):
Application calls for a 72-inch NPT Coaxial probe in
water with the bottom of the probe 10 inches above the
bottom of the tank. The user wants the 4 mA point at
24 inches and the 20 mA point at 60 inches as referenced
from the bottom of the probe.

In those applications in which it is desired to reference all
measurements from the bottom of the vessel, the value of
Lvl Ofst should be changed to the distance between the
bottom of the probe and the bottom of the vessel as shown
in Example 2.

Example 2:
Application calls for a 72-inch NPT coaxial probe in
water with the bottom of the probe 10 inches above the
bottom of the tank. The user wants the 4 mA point at
24 inches and the 20 mA point at 60 inches as referenced
from the bottom of the tank.

When the ECLIPSE transmitter is mounted in a
chamber/bridle, it is usually desirable to configure the unit
with the 4 mA (0%) point at the lower process connection
and the 20 mA (100%) point at the upper process connection.
The span is the center-to-center dimension. In this case, a
negative Lvl Ofst needs to be entered. In doing so, all
measurements are then referenced at a point up on the
probe as shown in Example 3.

Example 3:
Application calls for a 48-inch cage-coaxial flanged probe
measuring water in a chamber with the bottom of the
probe 6 inches below the lower process connection. The
user wants the 4 mA point to be 0 inches at the bottom
process connection and the 20 mA point to be 30 inches
at the top process connection.

10"

60"

20 mA

4 mA

24"

PrbModel

7xA-x

PrbMount

NPT

LvlUnits

in

Probe Ln

72 in

Lvl Ofst

0.0 in

Dielctrc

10-100

Set 4mA
24.0 in

Set 20mA

60.0 in

Example 1

10"

60"

20 mA

4 mA

24"

PrbModel

7xA-x

PrbMount

NPT

LvlUnits

in

Probe Ln

72 in

Lvl Ofst

10 in

Dielctrc

10-100

Set 4mA
24.0 in

Set 20mA

60.0 in

Example 2

6"

30"

4 mA

20 mA

PrbModel

7xR-x

PrbMount

Flange

LvlUnits

in

Probe Ln

48 in

Lvl Ofst

-6.0 in

Dielctrc

10-100

Set 4mA

0 in

Set 20mA

30.0 in

Example 3