Orion Instruments Eclipse 705 User Manual

Page 28

Advertising
background image

28

57-600 Eclipse

®

Guided Wave Radar Transmitter

2.6.5.3 Measurement Type: Interface Level (Loop Control = Interface Level)

Display

Action

Comment

21

SZ Fault
(select)

Select loop current behavior
when level is sensed in safety
zone

Safety Zone is a user-defined area just below the Blocking
Distance
. Enable Fault if necessary to ensure safe, reliable high-
level readings in critical applications. Choices are None, 3.6 mA,
22 mA, Latch 3.6 or Latch 22. If Latch 3.6 or Latch 22 is
selected, the loop current will remain in alarm until it is manually
cleared with the SZ Alarm Reset below (#23)

22

SZ Height

xx.x lu

Enter distance below
BlockDis where SZ Fault will
be asserted

Enter a distance value that develops a safety zone just below the
Blocking Distance. Here the unit will report a Safety Zone Fault
(#21) if the level rises into this area.

23

SZ Alarm Reset

Press Enter to clear a
latched Safety Zone alarm

Clear a latched Safety Zone alarm

24

Threshld
(select)

Select from CFD, Fixed

For interface, refers to threshold for upper level pulse. (Set to
Fixed for most common applications.)

25

IfcThrsh
(select)

Select from CFD, Fixed

Interface mode only. Threshold for interface level pulse. (Set to
CFD for most common applications.)

26

Poll Adr

xx

Enter HART polling address
number (0-63)

Select a HART poll address (0–63). Enter 0 for a single
transmitter installation. Poll address does not affect loop current.

27

Loop Mode

Enable/Disable

Determines whether the loop is fixed at 4.0 mA or controlled by
the PV.

28

Trim Lvl

xx.x lu

Enter value to adjust Level
reading

-10.0 inches <= Lvl Trim <= +10.0 inches
(Requires superuser password)

29

Trim 4

xxxx

Fine tune the 4 mA point

Adjust setting to output exactly 4.0 mA on current meter

30

Trim 20

xxxx

Fine tune the 20 mA point

Adjust setting to output exactly 20.0 mA on current meter

31

Loop Tst

xx.x mA

Enter a mA Output value

Set mA output to any given value to perform loop test

32

LvlTicks

xxxx

Diagnostic Display

Time of flight from fiducial to interface signal

33

IfcTicks

xxxx

Diagnostic Display

Interface mode only. Time of flight through upper liquid

34

Medium

Diagnostic Display

Interface mode only. Displayed messages are: Unknown,
Oil Only, Thin Oil, Thick Oil, Dry Probe

35

New Pass

xxx

Enter new password (0-255)

Displays encrypted value of present password

36

Language
(select)

Select from English, Spanish,
French, German

Language choice for LCD display. (no HART counterpart)

37

Mdl705HT
Ver3.0a0

Transmitter display

Product identification. Firmware version

38

DispFact
(select)

Select Yes to display factory
parameter menus

Access for viewing the factory parameter

39

History

(current status)

Press Enter to view history
of recent exceptions

Diagnostic Display

40

Run Time

41

History Reset

Press Enter and select yes
to clear history

Similar to SZ Alarm Reset

42

HF cable
(select)

Superuser Parameter

Select from 3-foot or 12-foot remote