 Make sure that there is at least 1" (25 mm) spacing

between the active probe rod and any part of the tank
(walls, stillwell, pipes, support beams, mixer blades, etc.).
Minimum stillwell diameter for Twin Rod probe is 3".

Ž Carefully place the probe into the vessel. Align the gasket

on flanged installations.

 Align the probe process connection with the threaded or

flanged mounting on the vessel.

 For threaded connections, tighten the hex nut of the probe

process connection. For flanged connections, tighten flange
bolts.

Refer to Bulk Solid Guidelines, Section 2.4.4.

Probe can be shortened in the field:

‘ a. Loosen and remove the two cable clamps.

b. Slide the weight off of the probe.

c. Cut the cable to the required length.

d. Remove 12 inches of the rib between the two cables.

e. Strip 6 inches of coating from the two cables.

f. Slide the weight back on to the probe.

g. Reinstall the two cable clamps and tighten.

h. Enter the new probe length (inches or cm) in software.

2.4.4.4 To install a Model 7x2 bulk solids flexible single rod

probe:

ΠMake sure the process connection is at least 2" NPT or a

flanged mounting.

 Carefully place the probe into the vessel. Align the gasket

on flanged installations.

Ž Align the probe process connection with the threaded or

flanged mounting on the vessel.

 For threaded connections, tighten the hex nut of the probe

process connection. For flanged connections, tighten flange
bolts.

 Probe can be shortened in field:
‘ a. Loosen and remove the two cable clamps.

b. Slide the weight off of the probe.

c. Cut the cable to the required length plus 6.38".

d. Slide the weight back on to the probe.

e. Reinstall the two cable clamps and tighten.

f. Enter the new probe length (inches or cm) in software.

15

57-600 Eclipse

®

Guided Wave Radar Transmitter

Model 7x5 Dual Rod

Bulk Solids Probe

Model 7x2 Single Rod

Bulk Solids Probe