Model 17800B / 17801B Recovery/Recycling/Recharging Unit

11

ENGLISH

The.“CL-L”.message.shows.on.the.display.if.there.is.pressure.in.the.unit,.and.a.

self-clearing.process.of.the.components.begins..You.can.press.

HOLD/CONT.to.

bypass.clearing.if.an.accurate.recovery.amount.is.not.required..Otherwise,.the.

compressor.will.start.and.the.“CL-L”.message.remains.on.the.display..This.process.

takes.from.20.seconds.to.four.minutes.to.complete..Once.the.clearing.is.complete,.

the.unit.automatically.begins.to.recover.refrigerant.from.the.system..If.there.is.no.

internal.pressure.in.the.unit,.refrigerant.recovery.begins.immediately.

CAUTION:

If the A/C system pressure is 25 psi or less, the

message “CH-P” appears on the display to alert you not to attempt

recovery from an empty system. Do not press HOLD/CONT to

continue the recovery process unless you know the A/C system

contains refrigerant.

The.display.shows.that.the.unit.is.in.the.RECOVER.mode.and.the.AUTOMATIC.

cycle..You.can.monitor.the.amount.of.refrigerant.removed.from.the.system.by.

watching.the.display..The.compressor.shuts.off.automatically.when.recovery.is.

complete.(at.approximately.13.inches.of.vacuum)..The.display.shows.the.“CPL”.

message,.and.then.alternately.flashes.the.weight.of.refrigerant.recovered.

. 5.. To.assure.complete.recovery.of.refrigerant,.wait.for.five.(5).minutes.and.

watch.the.manifold.gauges.for.a.rise.in.pressure.above.“0.”.If.a.rise.occurs,.

press.

HOLD/CONT..Repeat.as.needed.until.the.system.pressure.holds.for.

two.(2).minutes.

CAUTION:

Drain the oil from the separator only after each

recovery.

Do not completely depressurize the oil separator; immediately close

the valve when oil is completely drained in the next step. The lower

right corner of the display will indicate “OIL (OUNCES)” as a reminder.

. 6.. Verify.the.oil.catch.bottle.is.empty,.then.slowly open.the.oil.drain.valve,.

and.drain.the.oil.into.the.oil.catch.bottle..This.oil.was.removed.from.the.

A/C.system.during.recovery..It.must.be.replaced.with.new.oil..When.all.the.

recovered.oil.has.completely.drained,.immediately.close.the.valve.and.record.

the.amount.of.oil.in.the.bottle..Dispose.of.waste.oil.in.an.appropriate.manner.

If the recovery tank fills completely:
• The compressor shuts off; the digital display shows the message “FULL.”
• Change the tank.

The.A/C.system.is.now.empty..Make.any.repairs.at.this.time.

Weight Example

Operating Instructions

HOLD

OIL(OUNCES)

HOLD

LBS

RECOVER

Hold

HOLD

LBS

RECOVER

CL-L

HOLD

CH-P

CPL

8.30

FULL

FLASHES