Model 17800B/17801B Recovery/Recycling/Recharging Unit

21

ENGLISH

EVACUATION OVERVIEW

1. Verify the high- and low-side hoses are connected to the A/C-R

system, and that the high- and low-side valves are open.

2. Press

SHIFT/RESET to toggle the display to show “PROGRAM VACUUM

MINUTES 15.00.” Fifteen minutes is the default time for evacuation. To

change the time, press the appropriate keys to display the desired time. Then

press

ENTER.

Note: The longest time that can be programmed is 98.99 (98 minutes

and 99 seconds).

3. Press

VACUUM to start evacuation. The display counts down the time

remaining. If the message “U-HI” appears, there is 25 psi or greater of

pressure at the inlet. You must recover that pressure to continue. If necessary,

press

RECOVER.

4. When the programmed time has expired the vacuum pump automatically

shuts off and the display shows “CPL.”

To run the vacuum pump continuously, program the time to “99.00,” press

ENTER, then press VACUUM. The pump will start and the display will

show “CON AUTOMATIC VACUUM.” To turn the vacuum pump off, press

HOLD/CONT.

RECYCLING OVERVIEW

1. Verify both valves on the tank are open. Press and hold

SHIFT/RESET and

then press “1” to start the recycling process.

2. When the tank temperature equalizes (after about five minutes of recycling

time), purge non-condensables from the tank. To purge, use the temperature

gauge to determine the temperature of the refrigerant. Then use the pressure/

temperature chart on the top of the unit to determine the correct pressure for

that refrigerant. If the gauge pressure exceeds the target pressure by more

than 10 psi, open the air purge valve for about 30 seconds and release non-

condensables from the tank.

3. Close the air purge valve and let the tank stabilize (about 30 seconds). Check

the air purge gauge again. Repeat Steps 2 and 3 as necessary during the

recycling process.

4. Close the tank's LIQUID valve to stop the recycling process. The unit will

pull into a vacuum and shut off automatically.

CAUTION:

You can stop

recycling

instantly by

pressing HOLD/

CONT, then

SHIFT/RESET,

but this can

leave liquid

refrigerant in

the low side

of the unit.

Closing the

tank’s LIQUID

valve is the

recommended

method.

Operating Overview

VACUUM

PROGRAM

MINUTES

I5.00

VACUUM

PROGRAM

MINUTES

CPL

AUTOMATIC

VACUUM

Con