7. Cautions in Operation

7.2

Caution for when setting to 60% or more of RCP2-RA8 pressing current limit value

When the pressing current limit value, which determines the pressing force of the pressing operation, is
60% or less, continuous pressing and continuous operation are available.
Set the pressing current control value to the following.

Ɣ PCON Controller: Pressing setting in Position Table

The pressing current limit value can be set up to 70%.
When setting to a value from 60% to 70%, have a calculation to see if it satisfies the following operation
conditions to check if the continuous pressing and continuous operation are available. If continuous
pressing and continuous operation are not available, try to shorten the pressing duration and stop duration
so the setting satisfy the operational conditions.

[Operation conditions]

Ɣ&RQGLWLRQV 7KHSUHVVLQJGXUDWLRQRUWKHVWRSGXUDWLRQDJDLQVWWKHFXUUHQWFRQWUROYDOXHVKRXOGEH

less than the maximum duration.

Ɣ&RQGLWLRQV 7KHFRQWLQXRXVRSHUDWLRQDOWRUTXHLQF\FOHVKRXOGEH1PRUOHVV
Ɣ&RQGLWLRQV 7KHVWRSRUSUHVVLQJRIZKLFKWKHFXUUHQWFRQWUROYDOXHLVJUHDWHUWKDQVKRXOGEH

once in 1 cycle.

Caution: When operating with the pressing current limit value from 60% to 70%, make sure to satisfy

the operational condition.

Not satisfying the operation conditions may generate excessive heat on the motor and may

result in serious damage.

(1)

Operational Conditions

1) Condition 1

Either the pressing duration or the stop duration against the current limit value is less
than the maximum duration.

The maximum duration of pressing duration and stop duration against the current limit value is shown
in Table 1 and Graph 1.
Confirm that the pressing duration or stop duration against the current limit value is less than the
maximum duration.

0

200

400

600

800

1000

1200

1400

1600

1800

60

62

64

66

68

70

Table 1: Current Limit Value and Maximum Duration

Graph 1: Current Limit Value and Maximum Duration

Pressing/Stop

Current Limit Value [%]

60 or less

(Continuous Operation Available)

Maximum Duration [s]

Maximum Duration [s]

Current Limit Value [%]