REV 2 VCBA VERSION 10.xx SOFTWARE MANUAL

52

NOTES

• Contact Low is the fastest Close time of the circuit breaker main

contacts.

• Contact High is the slowest Close time of the circuit breaker main

contacts.

• Contact Delta, also known as Contact Spread, is the maximum time

between the fastest and slowest contact time.

• Resistor On Low is the fastest Close time of the circuit breaker insertion

resistor contacts.

• Resistor On High is the slowest Close time of the circuit breaker

insertion resistor contacts.

• Resistor On Delta is the maximum time between the fastest and the

slowest resistor contact time.

• Up to 20 characters can be entered in the Comment field.

After entering all the values, click on the “OK” button. The following window will be
displayed:

6. This dialog box is used to define the Contact and Resistor Close-Open Times or “Contact

Live Times” (in milli-seconds). Input the corresponding values for each field and click on
the “OK” button. The following window will be displayed: