1 fm approval, Fm approval -4, Caution – Yokogawa EJX210B User Manual

Page 12: Warning

Advertising
background image

<2. Handling Cautions>

2-4

IM 01C27C01-01EN

2.8 Installation of an Explosion-

Protected Instrument

If a customer makes a repair or modification to an

intrinsically safe instrument and the instrument is

not restored to its original condition, its intrinsically

safe construction may be compromised and the

instrument may be hazardous to operate. Please

contact Yokogawa before making any repair or

modification to an instrument.

CAUTION

This instrument has been tested and certified

as being intrinsically safe. Please note that

severe restrictions apply to this instrument’s

construction, installation, external wiring,

maintenance and repair. A failure to abide by

these restrictions could make the instrument a

hazard to operate.

WARNING

The battery pack may be replaced in a

hazardous area. The battery pack has

surface resistivity greater than 1G ohm and

must be properly installed in the enclosure

of the transmitter. Care must be taken during

transportation to and from the point of installation

to prevent electrostatic charge build-up.

2.8.1 FM Approval

Caution for FM intrinsically safe type. (Following

contents refer “DOC. No. IFM037-A20”)
Note 1. Model EJX Series Differential, gauge

and absolute pressure transmitters with

optional code /FS17 are applicable for use

in hazardous locations.

• Applicable Standard: Class 3600, Class

3610, Class 3611, Class 3810, NEMA 250,

ANSI/ISA-60079-0, ANSI/ISA-60079-11

• Intrinsically Safe for Class I, Division 1,

Groups A, B, C & D, Class II, Division 1,

Groups E, F & G and Class III, Division 1,

Class I, Zone 0, in Hazardous Locations, AEx

ia IIC

• Nonincendive for Class I, Division 2, Groups

A, B, C & D, Class II, Division 2, Groups F &

G and Class III, Division 1, Class I, Zone 2,

Groups IIC, in Hazardous Locations.

• Enclosure: NEMA 4X (Indoors and outdoors).

• Temperature Class: T4

• Ambient temperature: -50 to 70°C

Note 2. Installation

• Installation should be in accordance with

ANSI/ISA-RP12.06.01 and the National

Electric Code (NFPA 70).

• Dust-tight conduit seal must be used when

installed in a Class II, III, Group E, F and G

environments.

• Note a warning label worded

“SUBSTITUTION OF COMPONENTS MAY

IMPAIR INTRINSIC SAFETY,” and “INSTALL

IN ACCORDANCE WITH DOC. NO.

IFM037-A20”.

Transmitter

[Intrinsically Safe]

Class I, II, III, Division 1,

Groups A,B,C,D,E,F,G

Class I, Zone 0

in Hazardous (Classified)

Locations

AEx ia IIC

[Nonincendive]

Class I, II, Division 2,

Groups A,B,C,D,F,G

Class III, Division 1.

Class I, Zone 2, Group IIC,

in Hazardous (Classified)

Locations

Battery Pack

[Installation Diagram]

Amplifier housing code 7

Hazardous Location

F0210.ai

Transmitter

[Intrinsically Safe]

Class I, II, III, Division 1,

Groups A,B,C,D,E,F,G

Class I, Zone 0

in Hazardous (Classified)

Locations

AEx ia IIC

[Nonincendive]

Class I, II, Division 2,

Groups A,B,C,D,F,G

Class III, Division 1.

Class I, Zone 2, Group IIC,

in Hazardous (Classified)

Locations

Antenna

(*1)

Arrester

(*1, *2)

*1: These apparatus are simple apparatus.

*2: Arrester may not be connected.

Antenna Connector

Battery Pack

Amplifier housing codes other than 7

Hazardous Location

Note 3. Maintenance and Repair

• The instrument modification or parts

replacement by other than authorized

representative of Yokogawa Electric

Corporation is prohibited and will void FM

Approvals approval.

Advertising