<9. Maintenance>

9-15

IM 01C27C01-01EN

Integral

Indicator

Factory

NAMUR

category

Bit

Diagnostic

Status

Diagnostic Status Detail

Output actions

Pressure

Static

Pressure

Capsule

Temp

Value

Amp

Temp

Value

AL. 30

RANGE

O

Bit 22

Environmental

conditions out

of device

specification

DP_OUTSIDE_RANGE

Normal action Normal action Normal action Normal action

AL. 31

SP. RNG

SP_OUTSIDE_RANGE

Normal action Normal action Normal action Normal action

AL. 70

*6

LOWBAT

M

Bit 20

Power is

critical

low:

maintenance

need

short - term

WL_DEEPSLP_ALM

*3

Normal action Normal action Normal action Normal action

CRITICAL_LOWBAT

*4

AL. 70

*6

LOWBAT

Bit 19

Power is

low:

maintenance

need

mid - term

WL_LOWBAT_ALM

Normal action Normal action Normal action Normal action

AL. 60

AI OOS

C

Bit 24 O/S

AI1_OUT_OF_SERVICE Output value

(hold value)

Output status

(BAD: Out of

Service)

Normal action Normal action Normal action

AL. 61

AI OOS

AI2_OUT_OF_SERVICE

Normal action

Output value

(hold value)

Output status

(BAD: Out of

Service)

Normal action Normal action

AL. 62

AI OOS

AI3_OUT_OF_SERVICE

Normal action Normal action

Output value

(hold value)

Output status

(BAD: Out of

Service)

Output value

(hold value)

Output status

(BAD: Out of

Service)

AL. 63

AI SIM

C

Bit 17 Simulation is

active

SimulationActive

(AI1)

Normal action Normal action Normal action Normal action

AL. 64

AI SIM

SimulationActive

(AI2)

Normal action Normal action Normal action Normal action

AL. 65

AI SIM

SimulationActive

(AI3)

Normal action Normal action Normal action Normal action

*1: “Factory NAMUR category” refers to the four categories (C: Check function, M: Maintenance required, F: Failure, and O: Off

specification) according to NAMUR NE107*.

* NAMUR NE107 “Self-Monitoring and Diagnosis of Field Devices”

*2: When the device detects “AL01 CAP.ERR” and “AL02 AMP.ERR”, the LCD display stays on regardless of the status in LCD mode.

*3: Applicable for Integral antenna type (Amplifier housing code: 7).

*4: Amplifier temperature value is calculated in a normal way for Detachable antenna type (Amplifier housing code: 8 or 9).

*5: Applicable for Detachable antenna type (Amplifier housing code: 8 or 9).

*6:

When the ambient temperature is higher than 60°C, AL.70 may be generated despite the indication of Energy Left shows sufficiently

remained. However, it does not affect the device operation. This is caused by the change of battery inner status with extremely

low power consumption under high temperature environment. It is recommended to set the data updating period to 15 seconds or

shorter.