<8. Setting Parameters>

8-22

IM 01C27C01-01EN

(2) Span Adjustment

Span Adjustment is function to change the

input and output characteristic that assumed

the bottom value (zero point) of measurement

range as a standard.

Therefore, perform span adjustment

(adjustment of the upper limit value) after zero

adjustment (adjustment of bottom limit value).
After adding the pressure at point of adjustment

and setting pressure value as parameter, the

transmitter calculates quantity of adjustment

and performs adjustment automatically.
• Procedure to call up the lower limit value

parameter (Calibration Lowest Point).

AI1 block : Calibration Lowest Point
Set the lower limit adjustment value on the

differential pressure (AI1 block) Calibration

Lowest Point parameter screen. Apply a

reference pressure corresponding to the

lower limit of the measurement range to the

differential pressure/pressure transmitter

and set the reference pressure when it has

stabilized.

• Procedure to call up the calibration

adjustment parameter (Cal Cmd).

AI1 block : Cal Cmd : CAL_LOW
Set the lower limit of the measurement range

in CAL_LOW of the differential pressure

(AI1 block) Cal Cmd parameter.

• Procedure to call up the calibration status

parameter (Cal Status).

AI1 block : Cal Status
Confirm the value of CAL_SUCCESS (1)

using the Cal Status parameter.

• Procedure to call up the upper limit

adjustment parameter (Calibration Highest

Point).

AI1 block : Calibration Highest PointI
Set the upper limit adjustment value for the

differential pressure (AI1 block) Calibration

Highest PointI parameter. Apply a reference

pressure corresponding to the upper limit of

the measurement range to the differential

pressure/pressure transmitter and set the

reference pressure when it has stabilized.

• Procedure to call up the calibration

adjustment parameter (Cal Cmd).

AI1 block: Cal Cmd: CAL_HIGH
Set the upper limit of the measurement range

in CAL_HIGH of the differential pressure (AI1

block) Cal Cmd parameter.

• Procedure to call up the calibration status

parameter (Cal Status).

AI1 block: Cal Status
Confirm the value of CAL_SUCCESS (1)

using the Cal Status parameter.

(3) Adjustments for Static Pressure

For the EJX differential transmitters, zero point

and span adjustments of static pressure is

performed in the same way as with the primary

process variable (PV).

Adjustment should be performed using the

static pressure (AI2 block) Cal Cmd parameter.

After calibration, confirm the status by using the

static pressure (AI2 block) Cal Status.
• Procedure to call up the calibration

adjustment parameter (Cal Cmd).

AI2 block : Cal Cmd
Perform differential pressure zero/span

adjustment before static pressure zero/span

adjustment.

(4) Reset Adjustment

Reset Adjustment clear the amount of

adjustment. Reset Ajustment can be performed

using CAL_CLEAR of the differential pressure

(AI1 block) Cal Cmd parameter for the input

pressure and using CAL_CLEAR of the static

pressure (AI2 block) Cal Cmd parameter for the

static pressure. After Reset Adjustment, confirm

the status by using Cal Status of the cleared

block. The amount of adjustment made by the

external zero-adjustment screw can be reset to

the initial setting as well.
• Procedure to call up the calibration

adjustment parameter (Cal Cmd).

AI1, AI2 block : Cal Cmd : CAL_CLEAR