<7. Operation>

7-1

IM 01C27C01-01EN

7. Operation

7.1 Preparation for Starting

Operation

The EJX210B flange mounted differential pressure

transmitter measures the levels or densities of

liquids. This section describes the operation

procedure for the EJX210B as shown in Figure 7.1

when measuring a liquid level in an open tank.

NOTE

It is required to set security and network

information to enable the transmitter to be

connected to the Field Wireless Network. For

more details, refer to section 7.4 “Connecting to

the Field Wireless Network”.

(a) Confirm that there is no leak in the connecting

part of the transmitter mounting flange.

Remove the plastic dust cap placed in the

process connector (low pressure side).

(b) Insert batteries into the battery case, and install

to the transmitter. To insert batteries into the

battery case, be careful to polarity of batteries

and battery case. For details of Installation of

battery, refer to section 9.4.6 and 9.4.7.

Battery case is installed in the transmitter when

shipped from the factory, however, batteries are

sold separately and not included.

(c) Using the field wireless configuration tool or

the device configuration tool, confirm that

the transmitter is operating properly. Check

parameter values or change the setpoints as

necessary.

Integral Indicator’s indication can be used

to confirm that the transmitter is operating

properly. For details on how to confirm, refer to

subsection 8.4 “Self-Diagnostics.”

ISA100 devices display self-diagnostic information

in an easy-to-understand manner using four

categories (Check function, Maintenance required,

Failure, and Off specification) according to NAMUR

NE107*.

* NAMUR NE107 [ Self-Monitoring and Diagnosis of Field

Devices ]

F0701.ai

Open Tank

Figure 7.1

Liquid Level Measurement

Confirm that transmitter is operating properly

by integral indicator.

• If the transmitter is faulty, an error code is

displayed.

F0702.ai

Self-diagnostic error on integral indicator

(Faulity transmitter)

Figure 7.2

Integral Indicator with Error Code

NOTE

If any of the above errors are indicated on the

display of the integral indicator or the device

configuration tool, refer to subsection 9.5.3 for

corrective action.

■ Verify and Change Transmitter Parameter

Setting and Values

The parameters related to the following items are

minimum required to be set for operation, and set at

factory as specified in order. Confirm or change the

parameters if needed.