<7. Operation>

7-7

IM 01C27C01-01EN

7.6.4 Venting Gas for Flushing Connection

Ring

1) Gradually open the vent screw to vent gas from

the flushing connection ring.

2) When the flushing connection ring is completely

vented, close the vent screw.

3) Tighten the vent screw to a torque of 10 N·m

{1 kgf·m}.

F0713.ai

Vent screw

When you loosen the vent screw,

the accumulated liquid(or drain)

will be expelled in the direction

of the arrow.

Figure 7.9

Venting for Flushing Connection Ring

WARNING

Since the accumulated liquid (or gas) may be

toxic or otherwise harmful, take appropriate care

to avoid contact with the body, or inhalation of

vapors.