2 troubleshooting flowcharts, Troubleshooting flowcharts -8 – Yokogawa EJX210B User Manual

Page 70

Advertising
background image

<9. Maintenance>

9-8

IM 01C27C01-01EN

Abnormalities appear in measurement.

: Areas where self-diagnostic offers support

Is process variable

itself abnormal?

Inspect the

process system.

Isolate problem in

measurement system.

Does problem exist in

receiving instrument?

Check/correct

environmental conditions.

Inspect receiver.

Check transmitter.

Check/correct operating

conditions.

Measurement system problem

F0906.ai

YES

NO

NO

YES

Environmental conditions

Operating conditions

Transmitter itself

Figure 9.5.1 Basic Flow and Self-Diagnostics

9.5.2 Troubleshooting Flowcharts

Check display of the error code.

Check self-diagnostics by the device configuration tool.

Does the self-diagnostic

indicate problem location?

Contact Yokogawa service personnel.

F0907.ai

The following sorts of symptoms indicate that transmitter

may not be operating properly.

Example : • There is no output signal.

• Output signal does not change even though

process variable is known to be varying.

• Output value is inconsistent with value

inferred for process variable.

Fix pressure leaks, paying particular

attention to connections for impulse

piping,pressure-detector section, etc.

Is there any pressure leak?

YES

NO

YES

NO

Refer to Alarm Message Summary in

Subsection 9.5.3.

Is the Field Wireless Network

setting correct?

NO

YES

Reconnect to the Field Wireless

Network.

Advertising