<6. Wiring>

6-4

IM 01C27C01-01EN

6.1.2.3 Mounting of Arrester and Wiring

Mount an arrester between the extension cables

and connect the grounding cable to the grounding

terminal of the arrester as required.
Connect the grounding cable to the grounding

terminal on the transmitter body. Class C grounding

with the grounding resistance of 10 Ω or less is

necessary. Do not share the ground with other

devices.

F0605.ai

Transmitter side

Grounding cable

Antenna side

Antenna extension cable 2

Antenna extension cable 1

Arrester

Figure 6.5

Connection of the arrester and antenna

extension cable

F0606.ai

Transmitter side

Grounding cable

Antenna side

Protect by self-bonding tape

Figure 6.6

Arrester protection by self-bonding

tape

6.2 Grounding

When using the antenna extension cable with an

arrestor, Class C grounding with the grounding

resistance of 10 Ω is required. Always ground the

transmitter case in accordance with national and

local electrical codes. The most effective transmitter

case grounding method is a direct connection to

earth ground with minimal impedance.

CAUTION

Grounding is recommended for safe operation.

F0607.ai

Ground terminal

Figure 6.7

Ground Terminal