3 installation, 1 installation of the c520/c520n/c520x, Installation – INOR IPAQ R520X User Manual

Page 10: 1 installation of the c520/c520n/c520

Advertising
background image

3

INSTALLATION

C520/C520X / R520/R520X

09/2010 • 86B5200001

www.inor.com

10

3

Installation

3.1 Installation of the C520/C520N/C520X

The C520/C520X is intended for installation in DIN B connection heads or larger. The large

Ø7 mm / 0.28” center hole (see Chapter 6.1.3) facilitates the electrical connection of the

measurement sensor and the installation.

Figure 3: Connection head installation kit 70ADA00017

ATTENTION!
The C520 transmitter may not be installed in potentially explosive areas other than Zone 2 and

Division 2. For Zone 2/Div 2 applications a Class 2 power supply placed in safe area is needed.
In other potentially explosive areas, the C520X must be used.
The transmitter C520X must be supplied by an intrinsically safe power supply unit or Zener

barrier placed outside of the potentially explosive zone.

ATTENTION!
The C520X transmitter must be installed in a housing with the protection rating IP20 or better

according to EN 60529 / IEC 60529.
For Zone 2 applications the C520 must be mounted in an enclosure with at least IP54 according

to EN 60529 / IEC 60529.

1 Screw, M4

2 Spring

3 Lock washer

4 Pt100

5 Protective tube