ELECTRICAL CONNECTIONS

C520/C520X / R520/R520X

09/2010 • 86B5200001

www.inor.com

24

To calculate the maximum cable length for the output circuit, determine the total resistance of

the output loop (load resistance plus the approximate cable resistance). Find out the

capacitance of the cable being used. In the tables below you can find the maximum cable length

based on the typical values for 1 mm

2

cables. CN is the abbreviation for Capacitance Number

which is multiple of 5000 pF present in the device.

Field device

Cable insulation

PVC

Polyethylene

Polyethylene foam

1 (CN = 1)

600 m

1100 m

2000 m

10 multi-drop (CN = 1)

500 m

900 m

1600 m

10 multi-drop (CN = 4,4) 85 m

150 m

250 m

Table 1: Maximum length for typical 1 mm

2

cables

Insulation

Capacitance

PVC

300…400 pF/m

Polyethylene

150…200 pF/m

Polyethylene foam

75…100 pF/m

Conductors

Resistance

(both conductors in serie)

Area

Diameter

AWG

2.0

mm

2

1.6 mm

14

17

Ω/km

1.3

mm

2

1.3 mm

16

28

Ω/km

1.0

mm

2

1.15 mm

17

36

Ω/km

0.8

mm

2

1.0 mm

18

45

Ω/km

0.5

mm

2

0.8 mm

20

70

Ω/km

0.3

mm

2

0.6 mm

22

110

Ω/km

0.2

mm

2

0.5 mm

24

160

Ω/km

Table 2: Cable parameters

For multiple connections (multi-drop see the Figures 16), the following formula shall be used

L:

Cable length (m)

R:

Load resistance (incl. The resistance of any Zener barrier) + cable resistance (

Ω)

C:

Cable capacitance/meter (pF/m)

Cn: Number of C520/R520 transmitters in the loop

Cable length can be changed to ft. The capacitance has to be specified in pF/ft.