3.2 Installing the R520/R520N/R520X

The R520 / R520X transmitter is intended for installation on a top-hat rail according to

DIN EN 50022.

Figure 4: Rail installation

1

Fix the upper part of the transmitter onto the rail.

2

Press the lower part of the transmitter against the rail.

3

To remove the transmitter, use a screwdriver to bend the locking device using a small screwdriver.

Carefully pull the transmitter in the forward direction.


ATTENTION!
The R520 transmitter may not be installed in potentially explosive areas other than Zone 2 and

Division 2. For Zone 2/Div 2 applications a Class 2 power supply placed in safe area is needed.
In other potentially explosive areas, the R520X must be used.
The transmitter R520X can be installed in potentially hazardous area Zone 1 and 2 and the input

may be connected to Zone 0. R520X must be supplied by an intrinsically safe power supply unit

or Zener barrier placed outside of the potentially explosive zone.