4 output and input data, Output and input data, Technical data – INOR IPAQ R520X User Manual

Page 42

Advertising
background image

6

TECHNICAL DATA

C520/C520X / R520/R520X

09/2010 • 86B5200001

www.inor.com

42

6.2.4 Output and input data

Output terminals 6, 7

Input terminals 1, 2, 3, 4, 5

U

i

= V

max

:

≤ 30 VDC

U

o

= V

oc

:

≤ 6.6 VDC

I

i

= I

max

:

≤ 100 mA

I

o

= I

sc

:

≤ 26.4 mA

P

i

=P

max

:

≤ 900 mW

P

o

:

≤ 46 mW

L

i

:

10 µH

L

o

:

25 mH

C

i

:

12.1 nF

C

o

:

11 µF

Table 14: Electrical data for outputs-inputs of C520X

6.2.5 Ambient temperature data for areas with potentially explosive atmospheres

Temperature class

Ambient temperature

T6

-40°C

≤ T

a

≤ +60°C / 40°F ≤ T

a

≤ +140°F

T5

-40°C

≤ T

a

≤ +75°C / 40°F ≤ T

a

≤ +167°F

T4

-40°C

≤ T

a

≤ +85°C / 40°F ≤ T

a

≤ +185°F

Table 15: C520X temperature data