6 connection diagram, r520, Electrical connections – INOR IPAQ R520X User Manual

Page 22

Advertising
background image

4

ELECTRICAL CONNECTIONS

C520/C520X / R520/R520X

09/2010 • 86B5200001

www.inor.com

22

R

≥250 Ω

1

2

4

4

3

5

Test

4.6 Connection diagram, R520

ATTENTION!
IPAQ R520 is a Category 3 equipment and may only be installed in an area with a potentially

explosive atmosphere Zone 2 / Division 2 or it may be installed in safe area and connected to a

sensor located in an area with a potentially explosive atmosphere Zone 2 / Division 2!

1

Voltage supply 10…36 VDC

2

R

Load

, R

≥250 Ω

3

Input

4

Modem

5

Test connection (R

i

≤10 Ω)

Figure 13: R520 connection diagram

NOTE!
The HART modem is connected parallel to the output load or parallel to the output of the

transmitter (see Figure 13).