3 device management software’s, Device management software’s, Operation – INOR IPAQ R520X User Manual

Page 32

Advertising
background image

5

OPERATION

C520/C520X / R520/R520X

09/2010 • 86B5200001

www.inor.com

32

5.3.2 Configuration of the 520 series transmitters with handheld communicators FC 375/FC475

The Field communicators FC375/FC475 are handheld communicators from Emerson Process

Management for configuring HART and Foundation Fieldbus devices. To be able to configure the

transmitters with the FC 375/FC475 you need a Device Description (DD) file. The device driver is

possible to download from our website www.inor.com.

The transmitter DD has to be installed on the FC 375/FC475, otherwise the user will work with

the transmitter as generic device loosing opportunity to control all features of the transmitter.

For installing the DD on the FC 375/FC475 the “Easy Upgrade Programming Utility” is needed

and the FC375/FC475 must have a system card with “Easy Upgrade” option (see details in the

“375/475 Field Communicator User’s Manual”).

The transmitter DD for FC375/FC475 can also be downloaded from our website. For information

about installing, follow the instructions in the attached "readme.txt" file.

For proper connection of transmitters with the handheld communicator - see the Figures 7 and

13 for connection of the C520/R520 transmitters and figures 8 and 14 for connection of the

C520X/R520X transmitters.

5.3.3 Device management software’s

The 520 series transmitters can be configured via PC software’s such as AMS Device Manager

or Simatic PDM.

The AMS Device Manager is a PC application from Emerson Process Management for

configuring and managing HART and Foundation Fieldbus devices. For adaptation to different

devices AMS Device Manager uses Device Descriptions (DD).

The C520/C520X / R520/R520X Device Description has to be installed on the AMS System, and a

so called “Installation Kit C520/R520 HART AMS” is needed (available as download on the

internet).

For installing of the DD with the Installation Kit refer to the “AMS Intelligent Device Manager

Books Online" section "Basic AMS Functionality / Device Configurations / Installing Device

Types / Procedures / Install device types from media”. Please read also the “readme.txt”, which

is also contained in the Installation Kit.

The “Installation Kit C520/R520 HART AMS” can also be downloaded from our website

www.inor.com. For information about installing, follow the instructions in the attached

"readme.txt" file.

AMS supports the EDDL Process Variables Root Menu, the Diagnostic Root Menu and the Device

Root Menu for online access to the device.

The Simatic PDM is a PC application from Siemens for configuring HART and PROFIBUS

devices. For adaptation to different devices Simatic PDM uses Device Descriptions (DD).

The C520/C520X / R520/R520X Device Description has to be installed on the PDM System, and a

so called “Device Install C520/R520 HART PDM” is needed (available as download on the

internet).