KROHNE BM 102 Handbook User Manual
Page 15
BM
102
15
Fastening the probe to the tank bottom
Flexible probes can be fastened with a chuck (ring), turnbuckle or similar fastening device to the
tank bottom:
Chuck (ring)
Turnbuckle for Ø8 mm cable
probes
Turnbuckle for Ø4 mm cable
probes
Shortening cable probes
If required, the cable probe can be shortened, but this applies only when used in liquids.
Procedure
Step Action
1
Detach socket set screw M6x10 (ISO
4026) with a 3mm Allen (hexagon) key
(ISO 2936).
2
Pull cable (2) out of counterweight (3)
and shorten to required length using
cable cutters to prevent the cable wires
and strands from splaying out.
3
Insert cable back into counterweight and
tighten down screws
4
Change configuration parameters to new
probe length; the reference point is the
top edge of the weight (user menu
function 1.1.6)
Dimensions in mm (inches).