64

BM 102


Repeatability

± 2 mm or 0.08 “

Hysteresis none
Resolution

± 1 mm or 0.04 “

Transient recovery time

The transient recovery time to 1% deviation from the final value
amounts to approx. 4.6 times the programmed time constant.
However, the transient recovery time may differ if changes in
level are very rapid.

Start-up time

≤ 23 seconds

Long term drift

The long term drift is within the specified error of measurement.
Allow for the thermal expansion coefficient in the case of liquids
(organic liquids: ~0.15%/K)

Influence of ambient temperature
current output

HART

®

: typically

70

ppm/K

measured value

Approx.25 ppm (max. deviation over whole measurement range).

atmosphere

-1 ppm/K (above the liquid product).

digital

No influence on measured value due to regular self-calibration.


Environment

Ambient temperature

-30°C … +60°C or -20°F … +140°F***

Storage temperature

-40°C … +80°C or -40°F … +176°F

Environment class

Locations exposed direct to open-air climate, D1

Protection

IP 65 / NEMA 4 – 4X

Shock resistance

The device withstands the impact test in conformity with EN
61010, Section 8.2 with 0.5 J energy.

Vibration endurance limit

IEC 68-2-6 and prEN 50178
(10-57Hz: 0.075 mm / 57-150 Hz: 1 G).

Power supply

Standard

24 V DC,

Hazardous-duty (Ex, FM, …)

≤ 28 V DC

Range

18 … 35 V DC

Process

Process temperature, product

-30°C … +200°C or -22°F … +392°F * **

Process temperature, flange

-30°C … +90°C or -22°F … +194°F,
option +200°C or 390°F**

Process pressure,
standard

-1 … 16 bar or -14.5 … 232 psig; max. 40 bar or 580 psig at
20°C or 45°F***

Minimum dielectric constant

εr of product measured: probe type limits

Coaxial (type 3)

εr ≥ 1.4

Twin probe (type 4)

εr ≥ 1.8

Single probes (types 1, 2 & 6)

εr ≥ 2.1

Human interface

Communication, standard

Operator control and data display via PC using PCSTAR 2
software or HART

®

handheld communicator

Point-to-point

1 gauge connected to a PC or HHC

Multi-drop

Up to 5 gauges connected to a PC or HHC

*

see BM 102 MICROFLEX KEMA 00ATEX1101X Supplementary Installation and Operating

Instructions for Ex values

** higher or lower temperatures on request (non-Ex)
*** Subject to the process temperature and the mechanical properties of the process connection