BM

102

41


Function (Fct.)

Input Range

Description

2.0 CONFIG./TEST

2.1.0 OPERATION

2.1.1.0 BASIS PARAMETER

Enter 0 up to
60000 mm or 2362”

2.1.1.1 TANK HEIGHT

As per order

Tank height.
The tank height is defined as the
distance between the bottom of the
tank and the lower flange surface.

Enter 0 mm up to
< 24000 mm or
1063”

2.1.1.2 PROBE LENGTH

As per order

This value has to be equal to the
exact length of the probe. The only
situation for changing this value is if
the probe length has been changed.

Enter to
100 seconds

2.1.1.3 TIME CONSTANT

5 seconds

The time constant allows filtering of
possible signal fluctuations when the
product surface is turbulent.

2.1.1.4 DEAD ZONE

Enter a value
Fct.1.5.1(Detection
delay) … probe
length.

Warning : Critical Parameter

• Twin probe with

Probe length
<1 m or 3.3 ft
0.2 m or 8 in
• Single probe or

twin probe with
probe length
>1m or 3.3 ft

0.4 m or 16 in
• Coaxial probe

0 m or 0 in

Measurements near the flange may
not be precise or reliable.
Measurement may not be precise in
an area less than this recommended
value, depending on the probe type.

2.1.1.5 SENSOR INFO

2.1.1.5.1 Sensor upper limit

= Probe length

Read only Menu. Upper sensor limit.

2.1.1.5.2 Sensor lower limit

= 0

Read only Menu. Lower sensor limit.

2.1.1.5.3 Sensor min. span

= 1 mm or 0.04”

Read only Menu. Sensor minimum
span.

2.1.2.0 DISPLAY

2.1.2.1 LENGTH

Select m, cm, mm,
inch, Ft, optional
unit

2.1.2.1.1 LENGTH UNIT

mm

Length unit of displayed value (level /
distance).
The optional unit allows the user to
define a new unit (name and factor)
see menu 2.1.2.1.3

0, 1, 2, 3, 4, 5,
exponential format,
auto

2.1.2.1.2 DISPLAY FORMAT

2

Number of decimal places. Defines
the displayed length values format
(option of the HART

®

communicator

H275).