2 motion control – NORD Drivesystems BU0550 User Manual

Page 50

Advertising
background image

PLC logic for NORD SK 54xE frequency inverters

50

BU 0550 GB-0813

3.5.2

Motion Control

The Motion Control Lib is orientated to the PLCopen specification "Function blocks for motion control".

It contains function blocks (FB) for controlling and driving a frequency inverter and provides access to its
parameters.

Several settings must be made to the parameters of the frequency inverter in order for the Motion Blocks to
function.

Function block

Required settings

MC_MoveVelocity

P350 = PLC active

P351 = Main setpoint comes from the PLC

P553 [-xx] = Setpoint frequency

P600 = Position control (positioning mode) is switched off

MC_MoveAbsolute

P350 = PLC active

P351 = Main setpoint comes from the PLC

P600 = Position control (positioning mode) is switched on

The setpoint position High word must be parameterised in P553 [-xx] ( PLC_Setpoints )

The setpoint position Low word must be parameterised in P553 [-xx] ( PLC_Setpoints )

The setpoint frequency must be parameterised in P553 [-xx] ( PLC_Setpoints )

MC_MoveRelative

MC_MoveAdditive

MC_Home

MC_Power

P350 = PLC active

P351 = Control word comes from the PLC

MC_Control

MC_Reset

MC_Stop

Table 68 Settings for the Motion Control FB

HINWEIS

The PLC_Setpoints 1 to 5 and the PLC control word can also be described via process
variables. However, if the Motion Control FB is to be used, no corresponding process variables
may be declared in the table of variables, as otherwise the outputs of the Motion Control FBs
will be overwritten.

NOTE

Function blocks MUST be called up cyclically! This is important, as most functions in the func-
tion block are not processed within a single cycle.

NOTE

MC functions which are started via an EXECUTE input can not be stopped by resetting the
EXECUTE input!

Advertising