NORD Drivesystems BU0550 User Manual

Page 65

Advertising
background image

3 AWL (Instruction List, IL)

BU 0550 GB-0813

65

Fig. 8 Setpoint processing for FB PIDT1

Table 91 FB_PIDT1

VAR_INPUT

VAR_OUTPUT

Input

Explanation

Type

Output

Explanation

Type

ENABLE

Execute

BOOL

VALID

Output value is valid

BOOL

RESET

Reset outputs

BOOL

ERROR

Error in FB

BOOL

P

P component (Kp)

INT

ERRORID

Error code

INT

I

I component (Ki)

INT

MAXLIMIT

Maximum limit reached

BOOL

D

D component (Kd)

INT

MINLIMIT

Minimum limit reached

BOOL

T1

T1 component in ms

INT

OUTPUT

Output value

INT

MAX

Maximum output value

INT

MIN

Minimum output value

INT

SETPOINT

Setpoint

INT

VALUE

Actual value

INT

ERRORID

Explanation

0

No error

1600h

P component not within value range

1601h

I component not within value range

1602h

D component not within value range

1603h

T1 component not within value range

Δx

Setpoint

Value

-

+

+

K

p

K

d

,

T

1

K

i

Yd

Yi

Yp

Max limit

Min limit

Max limit - Yp

Min limit - Yp

Max limit

– Ypi

Min limit - Ypi

Ypi

Output

Advertising