5 information parameters – NORD Drivesystems BU0550 User Manual

Page 85

Advertising
background image

4 Frequency inverter details

BU 0550 GB-0813

85

4.1.5

Information parameters

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P740

… [-01]

… [-23]

PZD bus in

(Process data Bus In)

S

0 ... FFFF (hex)

This parameter informs about the actual control word and the setpoints that are transferred via
the bus systems or the PLC.

[-01] = Control word (P509)

Control word, source from (P509).

[-02] = Setpoint 1 (P510 [-01]) / (P546 [-01])

[-03] = Setpoint 2 (P510 [-01]) / (P546 [-02])

[-04] = Setpoint 3 (P510 [-01]) / (P546 [-03])

[-05] = Setpoint 4 (P510 [-01]) / (P546 [-04])

[-06] = Setpoint 5 (P510 [-01]) / (P546 [-05])

Setpoint data from main setpoint (P510 [-01]).

[-07] = Resulting status In Bit P480

"Resulting status In Bit P480":The displayed
value depicts all Bus In bit sources linked with
OR.

[-08] = Parameter data In 1

[-09] = Parameter data In 2

[-10] = Parameter data In 3

[-11] = Parameter data In 4

[-12] = Parameter data In 5

Data during parameter transfer: Order label
(AK), Parameter number (PNU), Index (IND),
Parameter value (PWE 1/2).

[-13] = Setpoint 1 (P510 [-02])

[-14] = Setpoint 2 (P510 [-02])

[-15] = Setpoint 3 (P510 [-02])

[-16] = Setpoint 4 (P510 [-02])

[-17] = Setpoint 5 (P510 [-02])

Setpoint data from master function value
(Broadcast), if P509/510 = 9 or 10
(P502/P503).

[-18] = Control word PLC

Control word, source PLC

[-19] = PLC setpoint 1

[-20] = PLC setpoint 2

[-21] = PLC setpoint 3

[-22] = PLC setpoint 4

[-23] = PLC setpoint 5

Setpoint data from the PLC.