4 frequency inverter details, 1 parameters, 1 operating displays – NORD Drivesystems BU0550 User Manual

Page 78: 2 control / plc parameters, 4 frequency inverter details 4.1 parameters

Advertising
background image

PLC logic for NORD SK 54xE frequency inverters

78

BU 0550 GB-0813

4 Frequency inverter details

4.1 Parameters

This section only lists parameters which are directly associated with the PLC function. Please refer to the
frequency inverter manual BU0500 / BU0505 for the full list of parameters.

4.1.1

Operating displays

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P001

Select of disp.value

(Selection of display value)

0 ...65

{ 0 }

Setting:

40 = PLC-Ctrlbox value, Visualisation mode for PLC communication

4.1.2

Control / PLC parameters

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P350

PLC functionality

(PLC functionality)

P

0 … 1

{ 0 }

Setting:

0 = Off: the PLC is not active, control of the frequency inverter is according to the

parameters (P509) and (P510)

1 = On: the PLC is active, control of teh frequency inverter is via the PLC, depending on

(P351). The definition of the main setpoints must be carried out accordingly in
parameter (P553). Auxiliary setpoints (P510[-02]) can still be defined via (P546).

P351

PLC Setpoint selection

(PLC Setpoint selection)

P

0 … 3

{ 0 }

Selection of the source for the control word and main setpoint with active PLC functionality
(P350 = 1). With the settings "0" and "1" definition of the main setpoints is via (P553), however
the definition of the auxiliary setpoints remains unchanged via (P546). This parameter is only
adopted if the frequency inverter is in the state "ready to start".

Setting:

0 = Control word and main setpoint =PLC: The PLC supplies the control word and the

main setpoint, parameters (P509) and (P510[-01]) have no function.

1 = Control word =P509: The PLC supplies the main setpoint, the control word

corresponds to the setting in parameter (P509)

2 = Main setpoint=P510[-01]: The PLC supplies the control word, the source for the main

setpoint corresponds to the setting in parameter (P510[-01])

3 = Control word and main setpoint=P509/P510: The source for the control word and the

main setpoint corresponds to the setting in parameter (P509)/(P510[-01])