PLC logic for NORD SK 54xE frequency inverters

70

BU 0550 GB-0813

3.5.7.2

FB_NMT

After a Power UP all CAN participants are in pre-operational bus status. In this state, they can neither
transmit nor receive a PDO. In order for the PLC to be able to communicate with other participants on the
CON bus, these must be set to an operational state. Usually, this is performed by the bus master. If there is
no bus master, this task can be performed by the FB_NMT.

The status of all participants which are connected to the bus can be controlled via the inputs PRE, OPE or
STOP. The inputs are adopted with a positive flank on EXECUTE. The function must be repeatedly called
up until the output DONE or ERROR has been set to 1.

If the output ERROR has been set to 1, there is either no 24V supply to the RJ45 CAN socket of the inverter
or the CAN driver of the inverter is in the status Bus off.

With a negative flank on EXECUTE all outputs are reset to 0.

Table 96 FB_NMT

VAR_INPUT

VAR_OUTPUT

Input

Explanation

Type

Output

Explanation

Type

EXECUTE

Execute

BOOL

DONE

NMT command is transmitted

BOOL

PRE

Sets all participants to
Pre-Operational status

BOOL

ERROR

Error in FB

BOOL

OPE

Sets all participants to
Operational status

BOOL

STOP

Sets all participants to
Stopped status

BOOL