3 AWL (Instruction List, IL)

BU 0550 GB-0813

57

3.5.2.7

MC_Home

Causes the frequency inverter to start a reference point run if EXECUTE changes from 0 to 1 (flank). The
frequency inverter moves with the setpoint frequency entered in VELOCITY. The direction of rotation is
reversed if the input with the position reference signal (P420[-xx] = Reference point) becomes active. With
the negative flank of the position reference signal the value in POSITION is adopted. Then the frequency
inverter brakes to 0Hz. The DONE signal changes to 1. During the entire HOME run the BUSY output is
active.

If the MODE input is set to 1, the FI remains at the middle of the initiator after a home run.

If the process is interrupted (e.g. by another MC function module), COMMANDABORTED is set.

In case of error, ERROR is set to 1. In this case, DONE is 0. The corresponding error code in the ERRORID
applies.

Table 77 MC_Home

3.5.2.8

MC_Power

The output stage of the frequency inverter can be switched on or off via this function. The output stage is
enabled if the ENABLE input is set to 1. The prerequisite for this is that the FI is in the status "Switch-on
block" or "Standby". If the FI is in the status "Error" or "Error reaction active", the fault must first be remedied
and acknowledged. Only then can enabling be carried out via this block. Switch-on is also not possible if the
frequency inverter is in the status "Not on standby". In all cases the FB goes into error status and ENABLE
must be set to 0 in order to acknowledge the error.

The frequency inverter is switched off if the ENABLE input is set to 0. If this happens while the motor is
running, it is first run down to 0Hz via the ramp set in P103.

The STATUS is 1, if the output stage of the frequency inverter is switched on. Otherwise it is 0.

ERROR and ERRORID are reset, if ENABLE is switched to 0.

Table 78 MC_Power

VAR_INPUT

VAR_OUTPUT

Input

Explanation

Type

Output

Explanation

Type

EXECUTE

Enable

BOOL

DONE

Specified setpoint position reached

BOOL

POSITION

Setpoint position

DINT

BUSY

Home run active

BOOL

VELOCITY

Setpoint frequency

INT

COMMAND-
ABORTED

Command aborted

BOOL

MODE

Home mode

BOOL

ERROR

Error in FB

BOOL

ERRORID

Error code

INT

ERRORID

Explanation

0

No error

1000h

FI is not enabled

1200h

Position control not activated

1201h

The High position has not been entered in the PLC setpoints (P553)

1202h

The Low position has not been entered in the PLC setpoints (P553)

VAR_INPUT

VAR_OUTPUT

Input

Explanation

Type

Output

Explanation

Type

ENABLE

Enable

BOOL

STATUS

Motor is supplied with current

BOOL

ERROR

Error in FB

BOOL

ERRORID

Error code

INT

ERRORID

Explanation

0

No error

1001h

Stop function is active

1300h

The FI is not in status "Standby" or "Switch-on block"