PLC logic for NORD SK 54xE frequency inverters

82

BU 0550 GB-0813

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P480

… [-01]

… [-12]

Funct. BusIO In Bits

(Bus I/O In Bits function)

S

0 … 80

all { 0 }

The Bus I/O In Bits are perceived as digital inputs. They can be set to the same functions
(P420).

These I/O bits can also be used in combination with the I/O extensions (SK xU4-

IOE) (Bit 4 …

7 and Bit 0 … 3)

[-01] = BusIn Bit0/IOE2 DIN1, Bus IO In Bit 0 or. DI 1 of the second SK xU4-IOE

[-02] = BusIn Bit1/IOE2 DIN2, Bus IO In Bit 1 or DI 2 of the second SK xU4-IOE

[-03] = BusIn Bit2/IOE2 DIN3, Bus IO In Bit 2 or DI 3 of the second SK xU4-IOE

[-04] = BusIn Bit3/IOE2 DIN4, Bus IO In Bit 3 or DI 4 of the second SK xU4-IOE

[-05] = BusIn Bit4/IOE1 DIN1, Bus IO In Bit 4 or DI 1 of the first SK xU4-IOE

[-06] = BusIn Bit5/IOE1 DIN2, Bus IO In Bit 5 or DI 2 of the first SK xU4-IOE

[-07] = BusIn Bit6/IOE1 DIN3, Bus IO In Bit 6 or DI 3 of the first SK xU4-IOE

[-08] = BusIn Bit7/IOE1 DIN4, Bus IO In Bit 7 or DI 4 of the first SK xU4-IOE

[-09] = Flag 1

[-10] = Flag 2

[-11] = Bit 8 BUS control word

[-12] = Bit 9 BUS control word

Setting:

80 = PLC Stop: Execution of the PLC program is stopped as long as the signal is present.

P481

… [-01]

… [-10]

Function BusIO Out Bits

(Function of Bus I/O Out Bits)

S

0 … 40

all { 0 }

The Bus I/O In Bits are perceived as digital outputs. They can be set to the same functions
(P434).

These I/O bits can also be used in combination with the I/O extensions (SK xU4-IOE)
(Bit 4 … 5 and Flag 1 … 2)

[-01] = BusOut Bit0, Bus IO Out Bit 0

[-02] = BusOut Bit1, Bus IO Out Bit 1

[-03] = BusOut Bit2, Bus IO Out Bit 2

[-04] = BusOut Bit3, Bus IO Out Bit 3

[-05] = BusOut Bit4/IOE1 DO1, Bus IO Out Bit 4 + DO1 of the first SK xU4-IOE

[-06] = BusOut Bit5/IOE1 DO2, Bus IO Out Bit 5 + DO2 of the first SK xU4-IOE

[-07] = BusOut Bit6/IOE2 DO1, Bus IO Out Bit 6 + DO1 of the second SK xU4-IOE

[-08] = BusOut Bit7/IOE2 DO2, Bus IO Out Bit 7 + DO2 of the second SK xU4-IOE

[-09] = Bit10 BUS status word

[-10] = Bit13 BUS status word

Setting:

40 = Output via PLC: The bit is set by the PLC