PLC logic for NORD SK 54xE frequency inverters

90

BU 0550 GB-0813

Index

Name

Function

Standardisation

Type

Access

62

_62_Inverter_32Bit_set_val1

Resulting 32Bit main setpoint 1 Bus

- Low word in P546[1]

- High word in P546[2]

_

DINT

R

63

_63_Inverter_32Bit_act_val1

FI 32Bit Actual value 1

- Low word in P543[1]

- High word in P543[2]

_

DINT

R

64

_64_Inverter_32Bit_lead_val1

32Bit master value 1

- Low word in P502[1]

- High word in P502[2]

_

DINT

R

65

_65_Broadcast_32Bit_set_val1 32Bit Broadcast Slave auxiliary set-

point 1

- Low word in P543[1]

- High word in P543[2]

_

DINT

R

66

_66_BusIO_input_bits

Incoming BusI/O data

- Bit1

– 8 = Bus I/O In Bit 0 – 7

- Bit 9 = Flag 1

- Bit 10 = Flag 2

- Bit 11 = Bit8 of the Bus control word

- Bit 12 = Bit9 of the Bus control word

_

INT

R

Table 106 Process values for bus setpoints and actual values

4.2.4

ControlBox and ParameterBox

The control boxes can be accessed via the process values listed here. This enables the implementation of
simple HMI applications.

Index

Name

Function

Standardisation

Type

Access

70

_70_Set_controlbox_show_val Display value for the

ControlBox

Display value = Bit 29

– Bit 0

Decimal point position = Bit 31 - Bit

30

DINT

R/W

71

_71_Controlbox_key_state

ControlBox keyboard status

Bit 0:

ON

Bit 1:

OFF

Bit 2:

DIR

Bit 3:

UP

Bit 4:

DOWN

Bit 5:

Enter

BYTE R

72

_72_Parameterbox_key_state

ParameterBox keyboard
status

Bit 0:

ON

Bit 1:

OFF

Bit 2:

DIR

Bit 3:

UP

Bit 4:

DOWN

Bit 5:

Enter

Bit 6:

Right

Bit 7:

Left

BYTE R

Table 107 ControlBox and ParameterBox process values

4.2.5

Info parameters

The most important actual values for the frequency inverter are listed here.

Index

Name

Function

Standardisation

Type

Access

80

_80_Current_fault

Number of actual fault

Error 10.0 = 100

BYTE

R

81

_81_Current_warning

Actual warning

Warning 10.0 = 100

BYTE

R

82

_82_Current_reason_FI_blocked

Actual reason for switch-on block
state

Problem 10.0 = 100

BYTE

R

83

_83_Input_voltage

Actual mains voltage

100 V = 100

INT

R

84

_84_Current_frequency

Actual frequency

10Hz = 100

INT

R

85

_85_Current_set_point_frequency1

Actual setpoint frequency from the
setpoint source

10Hz = 100

INT

R