NORD Drivesystems BU0550 User Manual

Page 86

Advertising
background image

PLC logic for NORD SK 54xE frequency inverters

86

BU 0550 GB-0813

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P741

… [-01]

… [-23]

PZD bus out

(Process data Bus Out)

S

0 ... FFFF (hex)

This parameter provides information about the actual status word and the actual values that
are transferred via the bus system.

[-01] = Bus status word (P509)

Status word

[-02] = Actual bus value 1 (P543 [-01])

[-03] = Actual bus value 2 (P543 [-02])

[-04] = Actual bus value 3 (P543 [-03])

[-05] = Actual bus value 4 (P543 [-04])

[-06] = Actual bus value 5 (P543 [-05])

Actual values

[-07] = Resulting status OutBit P481

"Resulting status OutBit P481":The displayed
value depicts all Bus Out bit sources linked
with OR.

[-08] = Parameter data Out 1

[-09] = Parameter data Out 2

[-10] = Parameter data Out 3

[-11] = Parameter data Out 4

[-12] = Parameter data Out 5

Data during parameter transfer: Order label
(AK), Parameter number (PNU), Index (IND),
Parameter value (PWE 1/2).

[-13] = Actual value 1 of master function

(P502[-01])

[-14] = Actual value 2 of master function

(P502[-02])

[-15] = Actual value 3 of master function

(P502[-03])

[-16] = Actual value 4 of master function

(P502[-04])

[-17] = Actual value 5 of master function

(P502[-05])

Actual value data from master function value
(P502/P503).

[-18] = Status word PLC

Status word via the PLC.

[-19] = Actual value 1 PLC

[-20] = Actual value 2 PLC

[-21] = Actual value 3 PLC

[-22] = Actual value 4 PLC

[-23] = Actual value 5 PLC

Actual value data via the PLC.

Advertising