HP Insight Management for Tivoli User Manual

Page 58

Advertising
background image

Appendix B: HP SNMP events 58


Trap types

Rules file Description

Netcool

severity

cpqRPMtrapUPSTemperatureOut
OfRange (21007)

21007

This event occurs when a UPS device
reports temperature is out of range.

Critical (5)

cpqRPMtrapUPSTemperatureOut
OfRangeCleared (21008)

21008

This event occurs when a UPS device
reports temperature is normal.

Clear (0)

cpqRPMTrapUPSShutdownPendi

ng (21011)

21011

This event occurs when a UPS device

reports a shutdown pending condition.

Major (4)

cpqRPMTrapUPSShutdownPendi

ngCleared (21012)

21012

This event occurs when a UPS device

reports a shutdown pending condition is
cleared.

Clear (0)

cpqRPMTrapUPSShutdownImmin

ent (21013)

21013

This event occurs when a UPS device

reports a shutdown imminent condition.

Critical (5)

cpqRPMTrapUPSShutdownImmin
entCleared (21014)

21014

This event occurs when a UPS device
reports a shutdown imminent condition is

cleared.

Clear (0)

cpqRPMtrapUPSOutputoutofRan

ge (21019)

21019

This event occurs when a UPS device

reports output voltage is out of range.

Critical (5)

cpqRPMTrapUPSOutputVoltage

Normal (21020)

21020

This event occurs when a UPS device

reports output voltage is normal.

Clear (0)

cpqRPMtrapUPSInputOutofRang

e (21021)

21021

This event occurs when a UPS device

reports input voltage is out of range.

Major (4)

cpqRPMtrapUPSInputOutofRang

eCleared (21022)

21022

This event occurs when a UPS device

reports input voltage is normal.

Clear (0)

cpqRPMTrapUPSLossOfRedunda

ncy (21023)

21023

This event occurs when a UPS device

reports a loss of redundancy.

Major (4)

cpqRPMTrapUPSLossOfRedunda

ncyCleared (21024)

21024

This event occurs when a UPS device

reports a loss of redundancy cleared or

configuration changed from N+1 to
Capacity.

Clear (0)

cpqRPMTrapUPSOnBuck

(21029)

21029

This event occurs when a UPS device

reports an On Buck condition.

Minor (3)

cpqRPMTrapUPSOnBoost

(21031)

21031

This event occurs when a UPS device

reports an On Boost condition.

Minor (3)

cpqRPMTrapUPSManualLoadDu

mped (21033)

21033

This event occurs when the UPS is powered

off with user interaction.

Major (4)

cpqRPMTrapUPSManualLoadDu
mpedCleared (21034)

21034

This event occurs when a UPS device
reports UPS output is restored.

Clear (0)

cpqRPMTrapUPSFanFailure
(21035)

21035

This event occurs when a UPS device
reports a fan failure.

Critical (5)

cpqRPMTrapUPSFanFailureClear
ed (21036)

21036

This event occurs when a UPS device
reports a fan failure is cleared.

Clear (0)

cpqRPMTrapUPSEPOInitiated

(21037)

21037

This event occurs when a UPS device

reports an Emergency Power Off (EPO)
command was received to shutdown the
UPS immediately. This command might

come from a local control panel or from a
remote source.

Critical (5)

Advertising